2. KM-1301SWH-E (water-cooled)<br />
APPROXIMATE ICE<br />
AMBIENT TEMP.<br />
WATER TEMP. (ºF/ºC)<br />
PRODUCTION PER 24 HR. (ºF/ºC) 50/10 70/21 90/32<br />
70/21 1330 603 1304 591 1239 562<br />
80/27 1310 594 1269 576 1189 539<br />
90/32 1304 591 1240 562 1165 528<br />
lbs./day kg./day 100/38 1281 581 1222 554 1096 497<br />
APPROXIMATE ELECTRIC<br />
CONSUMPTION<br />
70/21<br />
80/27<br />
90/32<br />
1780<br />
1780<br />
1780<br />
1780<br />
1780<br />
1780<br />
1799<br />
1810<br />
1806<br />
watts 100/38<br />
1790<br />
1786<br />
1830<br />
APPROXIMATE WATER<br />
70/21 1335 5.05 1425 5.40 1971 7.46<br />
CONSUMPTION PER 24 HR. 80/27 1404 5.31 1544 5.85 2324 8.80<br />
90/32 1425 5.40 1643 6.22 2335 8.84<br />
gal./day m 3 /day 100/38 1741 6.59 1805 6.83 2971 11.25<br />
FREEZING CYCLE TIME<br />
70/21<br />
80/27<br />
90/32<br />
31<br />
32<br />
32<br />
32<br />
33<br />
34<br />
34<br />
35<br />
36<br />
min.<br />
HARVEST CYCLE TIME<br />
100/38<br />
70/21<br />
80/27<br />
90/32<br />
33<br />
4.2<br />
3.8<br />
3.7<br />
34<br />
3.7<br />
3.0<br />
2.4<br />
38<br />
3.4<br />
2.9<br />
2.2<br />
min. 100/38<br />
3.1<br />
2.4<br />
2.1<br />
HEAD PRESSURE<br />
70/21 238 16.7 239 16.8 249 17.5<br />
80/27 239 16.8 240 16.9 256 18.0<br />
90/32 239 16.8 241 16.9 255 17.9<br />
PSIG kg/cm 2 G 100/38 244 17.2 244 17.2 267 18.8<br />
SUCTION PRESSURE<br />
70/21 50 3.5 51 3.6 52 3.6<br />
80/27 50 3.5 51 3.6 52 3.7<br />
90/32 51 3.6 52 3.7 53 3.7<br />
PSIG kg/cm 2 G 100/38 51 3.6 52 3.7 54 3.8<br />
TOTAL HEAT OF REJECTION FROM CONDENSER<br />
19,382 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]<br />
TOTAL HEAT OF REJECTION FROM COMPRESSOR 2,600 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]<br />
WATER FLOW FOR CONDENSER<br />
117 gal./h [AT 100ºF (38ºC) / WT 90ºF (32ºC)]<br />
PRESSURE DROP OF COOLING WATER LINE less than 10 PSIG<br />
Note:<br />
1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold<br />
should be used for reference only.<br />
2. We reserve the right to make changes in specifications and design without prior<br />
notice.<br />
33