To access an event record using the overlay:<br />

• Use Modbus function 06 to write the desired event number in Holding Register 40001.<br />

• Use Modbus function 04 to read the overlay registers, as tabulated below.<br />

Input Address Address Name/description of 16-bit value<br />

Register (decimal) (hexadecimal) (4 hexadecimal characters)<br />

30021 20 0014 Event Type (numeric code; see table below)<br />

30022 21 0015 SIM Module Address (channel number)<br />

30023 22 0016 Module Subaddress (not used)<br />

30024 23 0017 Event Time Stamp (high byte: hours; low byte: minutes)<br />

30025 24 0018 Event Date Stamp (high byte: month; low byte: day)<br />

30026 25 0019 Event Date Stamp (low byte-year)<br />

30027 26 001A Event Data (i.e., location)<br />

Note: Event Data (leak location, in Input Register 30027) uses the unit of measure selected for the system, as defined in Holding<br />

Register 40007.<br />

The TTDM-NMM communicates the event type (Input Register 30021) with a numeric code, as defined in the table below (See<br />

“Appendix 2 - Events Glossary” for further detail).<br />

Code Event type<br />

001 Leak<br />

002 New Leak<br />

003 Re-Alarm<br />

004 Service Req’d<br />

005 Cable Break<br />

006 YB Loop Break<br />

007 RG Loop Break<br />

008 Loop Imbalance<br />

009 SI H/W Error<br />

010 SI Comm Error<br />

011 System Restart<br />

012 System Power Down<br />

013 Leak relay Reset<br />

015 Leak Cleared<br />

016 Service Cleared<br />

017 Cable Restored<br />

018 SI H/W Recovered<br />

019 SI Comm Recovered<br />

020 SIM Normal<br />

021 System Normal<br />

022 Memory Cleared<br />

023 RTC/RAM Error<br />

024 Re-Alarm 8 Hours<br />

025 Re-Alarm 12 Hours<br />

026 Re-Alarm 24 Hours<br />

027 Alarm Silenced<br />

Hint: An event record can also be accessed with a single read function. Page 43 in the “Modbus Technical Reference” section<br />

provides a register map so the host system can be programmed to access events records directly.<br />

37