Selection<br />
<strong>TeSys</strong> contactors<br />
For utilisation categories DC-1 to DC-5<br />
Rated operational current (Ie) in Amperes, in utilisation category DC-1, resistive loads:<br />
Rated operational Number of poles Contactor rating (1)<br />
voltage connected in LC1- LC1- LC1- LC1- LC1- LC1- LC1- LC1- LC1- LC1-<br />
Ue series LP1-<br />
D09 D12 D18 D25 D32 D38 D40 D50<br />
DT20 DT25 DT32 DT40 DT60<br />
– +<br />
– +<br />
24 V 1 20 20 20 25 32 40 40 40 50 65<br />
2 20 20 20 25 32 40 40 40 50 65<br />
3 20 20 20 20 32 40 40 40 50 65<br />
4 – 20 20 – 32 40 – – 50 –<br />
48/75 V 1 20 20 20 25 32 40 40 40 50 65<br />
2 20 20 20 25 32 40 40 40 50 65<br />
3 20 20 20 25 32 40 40 40 50 65<br />
4 – 20 20 – 32 40 – – 50 –<br />
125 V 1 4 4 4 4 7 7 7 7 7 7<br />
2 20 20 20 25 32 40 40 40 50 65<br />
3 20 20 20 25 32 40 40 40 50 65<br />
4 – 20 20 – 32 40 – – 50 –<br />
225 V 1 1 1 1 1 1 1 1 1 1 1<br />
2 4 4 4 4 7 7 7 7 7 7<br />
3 20 20 20 25 32 40 40 40 50 65<br />
4 – 20 20 – 32 40 – – 50 –<br />
300 V 3 – – – – – – – – – –<br />
4 – 20 20 – 32 40 – – 50 –<br />
460 V 1 – – – – – – – – – –<br />
4 – – – – – – – – – –<br />
900 V 2 – – – – – – – – – –<br />
1200 V 3 – – – – – – – – – –<br />
1500 V 4 – – – – – – – – – –<br />
Rated operational current (Ie) in Amperes, in utilisation category DC-2 to DC-5, inductive loads:<br />
Rated operational Number of poles Contactor rating (1)<br />
voltage connected in LC1- LC1- LC1- LC1- LC1- LC1- LC1- LC1- LC1- LC1-<br />
Ue series LP1-<br />
D09 D12 D18 D25 D32 D38 D40 D50<br />
DT20 DT25 DT32 DT40 DT60<br />
– +<br />
– +<br />
24 V 1 20 20 20 25 32 40 40 40 50 65<br />
2 20 20 20 25 32 40 40 40 50 65<br />
3 20 20 20 25 32 40 40 40 50 65<br />
4 – 20 20 – 32 40 – – 50 –<br />
48/75 V 1 8 8 8 8 32 40 40 40 50 65<br />
2 20 20 20 25 32 40 40 40 50 65<br />
3 20 20 20 25 32 40 40 40 50 65<br />
4 – 20 20 – 32 40 – – 50 –<br />
125 V 1 2 2 2 2 3 3 3 3 4 4<br />
2 15 15 15 15 32 40 40 40 50 65<br />
3 20 20 20 25 32 40 40 40 50 65<br />
4 – 20 20 – 32 40 – – 50 –<br />
225 V 1 0.5 0.5 0.5 0.5 1 1 1 1 1 1<br />
2 2 2 2 2 3 3 3 3 4 4<br />
3 8 8 8 8 32 40 40 40 50 65<br />
4 – 20 20 – 32 40 – – 50 –<br />
300 V 3 – – – – – – – – – –<br />
4 – 8 8 – 32 40 – – 50 –<br />
1 – – – – – – – – – –<br />
460 V 4 – – – – – – – – – –<br />
900 V 2 – – – – – – – – – –<br />
Characteristics:<br />
pages 24505/2 to 24505/7<br />
24560_Ver2.20-EN.fm/2<br />
1200 V 3 – – – – – – – – – –<br />
1500 V 4 – – – – – – – – – –<br />