Characteristics<br />

<strong>TeSys</strong> control relays<br />

7<br />

Model d control relays<br />

Rated operational power of contacts (conforming to IEC 947-5-1)<br />

a.c. supply, categories AC-14 and AC-15<br />

Electrical durability (up to 3600 operating cycles/hour) on an inductive load such as the coil of an electromagnet: making<br />

power (cos ϕ 0.7) = 10 times the power broken (cos ϕ 0.4).<br />

V 24 48 115 230 400 440 600<br />

1 million operating cycles VA 60 120 280 560 960 1050 1440<br />

3 million operating cycles VA 16 32 80 160 280 300 420<br />

10 million operating cycles VA 4 8 20 40 70 80 100<br />

Millions of operating cycles<br />

1<br />

8<br />

7<br />

6<br />

5<br />

4<br />

3<br />

2<br />

1<br />

0,8<br />

0,7<br />

0,6<br />

0,5<br />

0,4<br />

0,3<br />

0,2<br />

0,1<br />

0,1 0,2 0,3 0,4<br />

0,6 0,8 1 2 3 4<br />

0,5 0,7 0,9<br />

6 8 10<br />

5 7 9<br />

Current broken in A<br />

d.c. supply, category DC-13<br />

Electrical durability (up to 1200 operating cycles/hour) on an inductive load such as the coil of an electromagnet, without<br />

economy resistor, the time constant increasing with the power.<br />

V 24 48 125 250 440<br />

1 million operating cycles W 120 90 75 68 61<br />

3 million operating cycles W 70 50 38 33 28<br />

10 million operating cycles W 25 18 14 12 10<br />

Millions of operating cycles<br />

1<br />

8<br />

7<br />

6<br />

5<br />

4<br />

3<br />

2<br />

1<br />

0,8<br />

0,7<br />

0,6<br />

0,5<br />

0,4<br />

0,3<br />

440 V<br />

250 V<br />

125 V<br />

48 V<br />

24 V<br />

0,2<br />

0,1<br />

0,1 0,2 0,3 0,4<br />

0,6 0,8 1 2 3 4<br />

0,5 0,7 0,9<br />

6 8 10<br />

5 7 9<br />

Current broken in A<br />

References :<br />

pages 24525/3 to 24525/<br />

5<br />

Dimensions :<br />

page 24537/2<br />

Schemes :<br />

page 24537/3<br />

Schneider Electric<br />

24526_Ver3.10-EN.fm/5