Characteristics<br />
<strong>TeSys</strong> control relays<br />
7<br />
Model d control relays<br />
Type CAD " CAD $ CAD<br />
low consumption<br />
Control circuit characteristics<br />
Rated control circuit voltage (Uc) V 12…690 12…440 $ 5…72<br />
Control voltage limits<br />
Operation With coil 50/60 Hz 0.8…1.1 Uc at 50 Hz – –<br />
type:<br />
0.85…1.1 Uc at 60 Hz – –<br />
standard, wide – 0.7…1.25 Uc 0.7…1.25 Uc<br />
range<br />
Drop-out 0.3…0.6 Uc 0.1…0.25 Uc 0.1…0.25 Uc<br />
Average consumption at 20 °C " 50/60 Hz (to 50 Hz) VA Inrush: 70 – –<br />
and at Uc<br />
Hold-in: 8 – –<br />
With standard coil W – Inrush or hold-in: 5.4 Inrush or hold-in: 2.4<br />
Operating time<br />
Between coil energisation and<br />
(at rated control circuit voltage - opening of the N/C contacts ms 4…19 35…45 45…55<br />
and at 20 °C)<br />
- closing of the N/O contacts ms 12…22 50…55 60…70<br />
Between coil de-energisation and<br />
- opening of the N/O contacts ms 4…12 6…14 10…15<br />
- closing of the N/C contacts ms 6…17 20 25<br />
Short supply failures<br />
Maximum duration without<br />
affecting hold-in of the device ms 2 2 2<br />
Maximum operating rate<br />
In operating cycles<br />
per second 3 3 3<br />
Mechanical durability<br />
In millions of operating cycles With coil 50/60 Hz (at 50 Hz) 30 – –<br />
type:<br />
standard $ – 30 30<br />
wide range<br />
Time constant L/R ms – 28 40<br />
References :<br />
pages 24525/3 to 24525/<br />
5<br />
Dimensions :<br />
page 24537/2<br />
Schemes :<br />
page 24537/2<br />
Schneider Electric<br />
24526_Ver3.10-EN.fm/3