Dimensions, mounting<br />

<strong>TeSys</strong> <strong>protection</strong> <strong>components</strong><br />

Magnetic motor circuit-breakers GV2-L and GV2-LE<br />

GV2-L GV-AD, AM, AN, AU, AS GV2-AK00<br />

Block GV-AD, AM, AN<br />

Block GV-AU, AS<br />

X1 Electrical clearance = 40 mm for Ue ≤ 415 V, (1) Maximum.<br />

or 80 mm for Ue = 440 V,<br />

or 120 mm for Ue = 500 and 690 V.<br />

X2 = 40 mm.<br />

Mounting of GV2-L Adaptor plate GK2-AF01<br />

On mounting rail AM1-DE200, On panel On pre-slotted mounting plate<br />

AM1-ED200 (35 x 15) AM1-PA<br />

7.5 mm height compensation plate<br />

GV1-F03<br />

GV2-LE GV-AD, AM, AN, AU, AS GV-AE<br />

Block GV-AD, AM, AN<br />

Block GV-AU, AS<br />

X1 Electrical clearance = 40 mm for Ue ≤ 690 V. (1) Maximum.<br />

Mounting of GV2-LE<br />

On 35 mm 7 rail On panel with adaptor plate GV2-AF02 On pre-slotted mounting On mounting rails DZ5-MB201<br />

plate AM1-PA<br />

c = 80 on AM1-DP200 (35 x 7.5)<br />

c = 88 on AM1-DE200, ED200 (35 x 15)<br />

Characteristics :<br />

pages 24523/2 and 24523/3<br />

References :<br />

page 24522/2<br />

Schemes :<br />

page 24527/5<br />