Table 2.4 Summary of Venice Gardens WTF Design Parameters 1ParameterValueNumber of vessels per unit 10Number of stages 1Design recovery, % 50Building 2Number of units 5Number of units at full-expanded capacity 5Number of vessels per unit 9Number of stages 1Design recovery, % 50Chlorine Contact Tank/ClearwellNumber of units 1Total volume, gal 42,000Transfer PumpsNumber of pumps 2TypeVertical turbineCapacity, gpm 1500Pump head, ft 38Motor size, hp 20Pump speedConstantFinished Water Storage TankNumber of tanks 3TypeCovered ground storageTotal volume, MG 5High Service PumpsNumber of pumps 3Capacity, gpm 1620Pump head, ft 162Motor size, hp 100Pump speedVariableNotes: 1 Information obtained through interviews with WTF staff and equipment inspection.FINAL - August 31, 2005 27H:\Client\SAR Co_SAR\6873C00 WATER SUPPLY MASTER PLAN UPDATE\Deliverables\TM 2 - Water System Assets\Final\TM2 Final.doc