12.07.2015 Views

VISION TOUCH THR

VISION TOUCH THR

VISION TOUCH THR

SHOW MORE
SHOW LESS
  • No tags were found...

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>VISION</strong> <strong>TOUCH</strong> <strong>THR</strong>CONNECTION TO RS-485 FOR TELENET OR MODBUS-RTU3.6Connect the earth to the GNDterminal of M3 in the console(functional earth). This connectionhelps to limit the effects of theelectromagnetic noise on thecontrol system. The groundconnection must be made in amanner consistent with applicableregulations.Connect the terminal (A) of M3 inthe console to signal A of theModbus line and the terminal (B)of M3 in the console to signal B ofthe Modbus line. Connect thebraid of the shielded cable to theterminal (GND) of M3 in theconsole. Use twisted cablesuitable for the transmission ofRS485 signals with minimumsection of 0.5 mm2 (e.g. Belden8762 cable). Avoid coupling withpower cables.1) Example of connection between the console and the Modbus line:It is recommended to connect a resistance equal to 120Ω between A and B at thebeginning and end of the line in case of communication problems.For a correct functioning the Master has to have a RS485 polarized.Pag. 17 USER AND MAINTENANCE MANUAL Rev. 01-13

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!