The Protection FunctionCharacteristics of the Pilot Wire ConnectionThe table below indicates the characteristics of the inter-device pilot wire connection:CharacteristicsValuesImpedance2.7 Ω per 300 mMaximum length300 mType of cableShielded twisted (Belden 8441 or equivalent)Permissible conductor cross-section 0.4 ...2.5 mm 2Interconnection limit on inputs Z3, Z4 and Z5(to downstream devices)Interconnection limit on outputs Z1 and Z2(to upstream devices)15 devices5 devicesNOTE: When using the Compact NSX ZSI function with circuit breakers in the Masterpact and CompactNS ranges, an RC filter, reference LV434212, must be added by a Masterpact or Compact NS circuitbreaker (see Compact NSX 100-630 A - Catalogue).The figure below shows the connection of the LV434212 filter:MasterpactZ3Z4Z5LV434212Compact NSXZ1Z2Testing the ZSI FunctionConnection and operation of the ZSI function can be tested using the LTU software.LV434104 <strong>09</strong>/20<strong>09</strong> 53