13.07.2015 Views

The IT earthing system (unearthed neutral) in LV

The IT earthing system (unearthed neutral) in LV

The IT earthing system (unearthed neutral) in LV

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

c <strong>The</strong> correspond<strong>in</strong>g contact voltage isU C =R pe I d , i.e.:v if one of the faults is on the neutralmU =0,8U ,c 0 or21 ( + m)v if the double fault concerns two phasemconductors U c=0,8eU021 ( + m ).NB: this method is not applicable for <strong>in</strong>stallationssupplied by generator set, as, due to highgenerator impedance compared with theimpedance of the supplied network, voltage atthe orig<strong>in</strong> of the network <strong>in</strong> question is low whena fault occurs (> 400 0.02 0.08Fig. 16 : maximum break<strong>in</strong>g time specified for the <strong>IT</strong><strong>earth<strong>in</strong>g</strong> <strong>system</strong> by <strong>in</strong>stallation standards (* for s<strong>in</strong>glephasenetworks).c Protection of the neutral conductor when it isdistributed.Figure 3b shows that when a double fault occurs,the two SCPDs detect the fault current but eachone on a s<strong>in</strong>gle phase or on the neutral.This situation calls for particular monitor<strong>in</strong>g ofSCPD characteristics: this is because if thecables of the two feeders have similar crosssections,the two SCPDs play an equal role <strong>in</strong>break<strong>in</strong>g, but if the cross-sections are different,there is a risk of only one SCPD, the one withCahier Technique Schneider Electric no. 178 / p.16

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!