The IT earthing system (unearthed neutral) in LV

The IT earthing system (unearthed neutral) in LV

The IT earthing system (unearthed neutral) in LV

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

a) b)I dI dNNPENSCPDPESCPDR BU dR dR BU dR dc)I d12N3NPENPEPESCPDR BU dR dFig. 1 : <strong>in</strong>sulation fault on a network operated <strong>in</strong> TN-C [a], TN-S [b] and TN-C-S [c].NRCDI dProtection is provided by the Residual CurrentDevices (RCD): the faulty part is disconnectedas soon as the threshold I∆n, of the RCD placedupstream, is overshot by the fault current, so thatI∆n R B iU L .R B R AU dR dFig. 2 : <strong>in</strong>sulation fault on a network operated <strong>in</strong> TT.<strong>The</strong> <strong>IT</strong> <strong>system</strong>c Its pr<strong>in</strong>ciple:v the transformer neutral is not earthed, but istheoretically <strong>unearthed</strong>. In actual fact, it isnaturally earthed by the stray capacities of thenetwork cables and/or voluntarily by a highimpedance of around 1,500 Ω (impedanceearthedneutral);v the electrical load frames are earthed.Cahier Technique Schneider Electric no. 178 / p.5