WLCP-36WST-S3
WLCP-36WST-S3 - Douglas Lighting Control
WLCP-36WST-S3 - Douglas Lighting Control
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>WLCP</strong>-<strong>36WST</strong>-<strong>S3</strong><br />
WRS-2224 Relay Scanner<br />
Switch Inputs<br />
Input Connections<br />
Connect the external group switching devices to the scanner's group<br />
inputs. If you are connecting 24V contact switching devices other<br />
than a Douglas switch or time clock, you must first configure the<br />
input for a 24V contact. Use the keyboard on the scanner, as<br />
detailed in 'Input Configuration' on page 48.<br />
A maximum of 6 switching devices can be connected in parallel to<br />
the same master input, with a maximum wire length of<br />
2000'/600m if using 18 AWG wire.<br />
After all the output relays have been assigned to lighting loads,<br />
determine which relays are to be switched together as groups.<br />
Use the keypad built into the front surface of the scanner to assign<br />
relay groups to be switched by each input. Refer to the scanner<br />
PROGRAMMING pages of this manual and the directions printed<br />
on the scanner for details.<br />
Switching with Momentary<br />
Contacts that use Diodes<br />
ON & OFF switching with contacts from another<br />
device or system is best accomplished with<br />
momentary type contacts that have a diode<br />
connected in series (one contact and diode for ON<br />
and another for OFF).<br />
Momentary contacts that utilize diodes have 2<br />
advantages:<br />
1. It is possible to have repeat ON or OFF<br />
commands. For example, during the night, an<br />
OFF signal could be issued every hour to ensure<br />
lights are swept OFF.<br />
2. Douglas relay switches can be connected in<br />
parallel for convenient override.<br />
Momentary contacts with diodes mimic the<br />
Douglas relay switch. Thus, the default input<br />
configuration of the WRS-2224 scanner is for<br />
the Douglas WR-8501 relay switch.<br />
Switching with 24V<br />
Momentary or Maintained<br />
Contacts (no Diodes)<br />
Inputs for the WRS-2224 can also be configured to<br />
accept 24V signals that have no diode connected.<br />
The signal can be momentary or maintained.<br />
When using the 24V contact control, be aware<br />
there are some restrictions. An input can be<br />
configured to switch relays ON when 24V is applied<br />
and OFF when it is removed. However, when this<br />
is the case it is not possible to send repeat OFF<br />
signals without an intervening ON signal. You can<br />
also configure the input so that only OFF signals<br />
are sent if a repeat signal is desired, although in<br />
this case there would be no ON signal. Should<br />
repeat OFF as well as ON signals be needed, then<br />
two 24V contacts would be needed with two<br />
inputs, one for the OFF signal and one for the ON.<br />
Refer to 'Input Configuration Mode' on page 6 for<br />
all the settings available for 24V contact control.<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
7<br />
8<br />
9<br />
10<br />
11<br />
12<br />
Momentary ON Contact<br />
OFF Contact<br />
ON<br />
Diode<br />
OFF<br />
Diode<br />
Master Sw Override<br />
Red<br />
Douglas switch OK with<br />
momentary contacts.<br />
NOT OK with maintained<br />
contacts.<br />
Maintained Form C<br />
Contact Set<br />
Coil<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
7<br />
8<br />
9<br />
10<br />
11<br />
12<br />
NO NC<br />
COM<br />
13<br />
14<br />
15<br />
16<br />
17<br />
18<br />
19<br />
20<br />
21<br />
22<br />
23<br />
24<br />
WRS-2224<br />
Relay<br />
Scanner<br />
13<br />
14<br />
15<br />
16<br />
17<br />
18<br />
19<br />
20<br />
21<br />
22<br />
23<br />
24<br />
W B<br />
1<br />
2<br />
3<br />
Switch<br />
Inputs<br />
B 45<br />
B<br />
ON Diode<br />
OFF Diode<br />
Components <strong>WLCP</strong>-<strong>36WST</strong>-<strong>S3</strong> 1.1<br />
page 46<br />
(OR)<br />
B<br />
W<br />
Tr<br />
Douglas Relay Switches<br />
The inputs of the WRS-2224 scanner<br />
are compatible with all models of<br />
Douglas relay switches. However, If<br />
you are connecting a different switch<br />
type, you must re-configure the input<br />
before connecting the switch. Follow<br />
the procedure described in the 'Input<br />
Configuration' section of this manual.<br />
When connected to the scanner, the<br />
LEDs of a Douglas switch will show the<br />
state of the relay group. If any of the<br />
relays in the group are ON, the group<br />
is defined as being ON and the red LED<br />
is lit. Only when all of the relays in the<br />
group are OFF is the group defined as<br />
being OFF and the green LED is lit.<br />
Take care when using Douglas WR-<br />
8501 switches. The WR-8501 push<br />
button switch will always send a signal<br />
that is opposite to its displayed state. If<br />
repeat ON or OFF control is desired, use<br />
the WR-8001 rocker switch which is<br />
able to select an ON or OFF signal.<br />
Douglas Timer Automation<br />
The inputs of the WRS-2224 scanner<br />
are compatible with Douglas timers<br />
such as the WTP-4408. When<br />
connecting a Douglas timer to the WRS-<br />
2224 scanner, the input must be<br />
configured for a Douglas relay switch<br />
(default).<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
7<br />
8<br />
9<br />
10<br />
11<br />
12<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
7<br />
8<br />
9<br />
10<br />
11<br />
12<br />
13<br />
14<br />
15<br />
16<br />
17<br />
18<br />
19<br />
20<br />
21<br />
22<br />
23<br />
24<br />
WRS-2224<br />
Relay<br />
Scanner<br />
Switch<br />
Inputs<br />
13<br />
14<br />
15<br />
16<br />
17<br />
18<br />
19<br />
20<br />
21<br />
22<br />
23<br />
24<br />
WR-8001 Rocker Switch<br />
W B<br />
1<br />
2<br />
3<br />
B 45<br />
B<br />
Red<br />
WR-8501 Pushbutton<br />
Switch with<br />
ON & OFF LEDs<br />
Esc<br />
WTP-4408<br />
A B C D<br />
1 2 3<br />
1 2 3<br />
4 5 6<br />
0<br />
5 A I H<br />
5 A I H<br />
47 58 69<br />
7 0 8 9<br />
Red<br />
Red<br />
Time Clock<br />
Maximum:<br />
6 switches<br />
9<br />
<br />
!<br />
"#$%&<br />
9<br />
*<br />
Clr<br />
B<br />
W<br />
Tr<br />
lighting controls