06.12.2012 Views

Liebert Mini-Mate2, 8 Ton - Emerson Network Power

Liebert Mini-Mate2, 8 Ton - Emerson Network Power

Liebert Mini-Mate2, 8 Ton - Emerson Network Power

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

17<br />

Site Preparation and Installation<br />

2.4.4 Electrical Connections, Evaporator or Chilled-Water Unit<br />

! WARNING<br />

Unit contains hazardous electrical voltage. Disconnect power supply before working<br />

within. Line side of factory disconnect remains energized when disconnect is off.<br />

! WARNING<br />

UNIT CONTAINS HAZARDOUS ELECTRICAL VOLTAGE. More than one disconnect<br />

may be required to remove power. Evaporator and condensing units may have separate<br />

disconnects. Open all disconnects before working within.<br />

Each unit is shipped from the factory with internal wiring completed. Refer to electrical schematic,<br />

Figure 11, Figure 25, and Figure 26 when making connections. Electrical connections<br />

to be made at the installation site are:<br />

• <strong>Power</strong> supply to each ceiling unit and control wiring between the evaporator unit and the condensing<br />

unit, if applicable.<br />

• Control wiring between the control panel (wallbox) and the evaporator or chilled-water unit<br />

control board.<br />

<strong>Power</strong> Connections<br />

All power and control wiring and ground connections must be in accordance with the National<br />

Electrical Code (NEC) and local codes. Refer to Unit serial tag data for electrical requirements.<br />

! CAUTION<br />

Use copper wiring only. Make sure that all connections are tight.<br />

Voltage supplied must agree with the voltage specified on the unit serial tag. A field supplied disconnect<br />

switch may be required. Consult local code.<br />

Route the electrical service conduit through the hole provided in the cabinet and terminate it at<br />

the electric box. Make connections at the factory terminal block or disconnect switch, L1, L2, L3.<br />

Connect earth ground to lug provided. See transformer label for primary tap connections.<br />

Installer will need to change transformer primary taps if applied unit voltage is other than prewired<br />

tap voltage.<br />

An optional single point power kit is available for units that are close coupled (refer to Figure 11<br />

and 2.4.3 - Piping Connections and Coolant Requirements). This kit should be mounted<br />

inside the evaporator unit before installing the unit in the ceiling. Specific installation instructions<br />

are included with the single point power kit.<br />

Control Connections (10-wire on air-cooled, 8-wire on water/glycol cooled)<br />

A field-supplied control connection (24 VAC) is required between the evaporator and the condensing<br />

unit. Control wiring must be installed in accordance with the National Electrical Code (NEC)<br />

Class 2 circuit. Glycol-cooled units also require a two-wire control connection to the drycooler and<br />

pump.<br />

Control wiring between the evaporator and the condensing unit must not allow a voltage drop in<br />

the line of more than 1 volt (16 gauge minimum for 75 feet). Do not connect additional electrical<br />

devices to the control circuit. The internal control transformer is only sized for factorysupplied<br />

components.<br />

Additional control wiring will be required if your system includes other optional monitoring and<br />

control devices.<br />

Four (4) wire (thermostat type) must be connected between the evaporator control board and the<br />

wall box. See Figure 25 and Figure 26 and see Figure 11 for electrical connections.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!