Figure 13 Indoor air-cooled centrifugal condensing unit dimensions and pipe connections<br />

Customer supplied<br />

threaded rods for module<br />

support from ceiling (1/2"<br />

minimum diameter<br />

recommended) (typ. 4).<br />

13/16"<br />

(21mm)<br />

23 7/8 "<br />

(606mm)<br />

NOTE: Unit is spaced evenly in<br />

reference to threaded<br />

rod centers.<br />

Single Point <strong>Power</strong> Kit<br />

connection from Evaporator.<br />

System 1 (3<strong>Ton</strong>) Suction Line Connection,<br />

Aeroquip #11 Male.<br />

System 2 (5<strong>Ton</strong>) Suction Line Connection,<br />

Aeroquip #12 Male.<br />

System 1 (3<strong>Ton</strong>) Liquid Line Connection,<br />

Aeroquip #6 Male.<br />

System 2 (5<strong>Ton</strong>) Liquid Line Connection,<br />

Aeroquip #10 Male.<br />

42 17/32 "<br />

(1080.3mm)<br />

THREADED ROD<br />

CENTERS<br />

66 9/32 "<br />

(1683.5mm)<br />

CABINET<br />

DIMENSION<br />

59 13/16 "<br />

(1519mm)<br />

9/16" (14mm) dia. holes for<br />

threaded rods (typ. 2 each end)<br />

Air Inlet<br />

1 13/16 "<br />

(40mm)<br />

7/8" (22.2mm) dia. knockout<br />

electrical entrance for alternate<br />

control panel low voltage routing.<br />

21<br />

Air Outlet<br />

40 5/32 "<br />

(1020mm)<br />

CABINET<br />

DIMENSION<br />

64 1/4 "<br />

(1632mm)<br />

THREADED ROD<br />

CENTERS<br />

19 1/32 "<br />

(483mm)<br />

Hanger<br />

Bracket<br />

7/8" (22.2mm) dia. electrical entrance<br />

for low voltage connection.<br />

Site Preparation and Installation<br />

8 13/16 "<br />

(224mm)<br />

16 5/16 "<br />

(414mm)<br />

1 3/32 "<br />

(26mm)<br />

26 3/8 "<br />

(670mm)<br />

Shaded area indicates a<br />

recommended clearance of<br />

30" (762mm) for component<br />

access and removal.<br />

7/8" (22mm) & 1 1/8" (29mm)<br />

dia. knockouts electrical entrance<br />

for high voltage connection<br />

DPN000248_Rev1