Table 18 Troubleshooting (continued)<br />

Symptom Possible Cause Check or Remedy<br />

Cooling cycle too<br />

short<br />

Display freezes<br />

and control pads<br />

do not respond<br />

Condensate<br />

pump does not<br />

operate<br />

Continuous<br />

Cooling<br />

Continuous<br />

Heating<br />

Dehumidification<br />

Humidification<br />

Sensor response delay too<br />

short<br />

Static discharge<br />

Open or short circuit in<br />

wiring<br />

Failed temperature sensor<br />

Shorted wiring or failed<br />

control board<br />

59<br />

Troubleshooting<br />

Increase sensor response delay. See 3.12 - Calibrate Sensors.<br />

During period of low humidity, static electricity can cause the control<br />

program to freeze or display incorrect information. Although this is<br />

unlikely, the control can be reset by cycling power from the disconnect<br />

switch.<br />

Find open or short circuit and repair power to pump.<br />

Temperature display will indicate dashes. Check wiring from<br />

temperature/humidity board (remote sensors) to the control board or<br />

from control board to wallbox. Replace temperature/humidity circuit<br />

board (remote sensors) or wallbox.<br />

Check wiring and/or replace control board.