atw Vol. 63 (2018) | Issue 8/9 ı August/September
RESEARCH AND INNOVATION 460
| | Fig. 4.
Tempearature and Hydrogen Concetration at the Exit of Test Device of Periodic Inspection
(New Catalyst: 3 % hydrogen and air mixture at 60 °C and 1 bar).
shows temperature rise behavior of
new catylists, which shows a similar
trend with time. Therefore, the PAR
supplier suggested the accepatance
criteria of the periodic inspection as
the temperature rise at a given time
(The exact values of temperature rise
and time are not described in this
paper because that information is a
supplier’s proprietary). Figure 5
shows temperature rise bebavior of
catylists that were exposed to containment
air during one overhaul period.
The behavior of temperature rise is
affected by the existence of VOC.
Some catalysts showed delayed startup
of hydrogen recombination and
others showed further increase of
temperature by combustion of VOC
itself. Figure 5 also shows the hydrogen
volume faction of air-hyrogen
mixture at the outlet of the test device.
It showed that the hydrogen recombination
already started although
the temperature does not reach the
required value. Therefore, there is a
possibility of unneccesary failure of
plant inspection with the current
method by temperature rise. This
method requires relatively long test
time because of larger heat capacity of
ceramic structure. In addition, it is
difficult to correlate the hydrogen
recombination performance with the
amount of temperature rise and test
time. Threfore, we decided to change
the inspection method from the temperature
rise to the direct measurement
of hydrogen concentration with
new acceptance criterion.
Under the VOC-affected conditions,
the performance of PAR is hard
to identify through the current perioic
inspection method because the startup
delayed time and the hydrogen
removal rate are defined under the
| | Fig. 5.
Tempearature and Hydrogen Concetration at the Exit of Test Device of Periodic Inspection
(After the Exposue of One Overhaul Period to Containment Air, 3 % hydrogen and
air mixture at 60 °C and 1 bar).
natural convection conditions. Therefore,
a number of catalysts are withdrawn
out of containment during an
overhaul period of each plant and
their performance is tested in the PAR
performance test facility (PPTF) under
the natural convection conditions.
A total of 152 tests are performed
with 608 catalyst samples to investigate
the effect of volatile organic
compounds (VOC) on the startup
performance on the hydrogen
removal. The catalyst samples are
taken from seventeen (17) plants with
four (4) different reactor types. For
plants C, D, F, H and M, the tests are
performed twice in the first and
second outage period to compare test
resuts between the first and the
second outages in the same plant.
Figure 6 shows the measured start-up
delay times in conditions of hydrogen
of 3 vol. %, temperature of 60 °C and
pressure of 1.5 bar. These test conditions
are selected because a start-up
delay time is considered after the
hydrogen concentration and the
temperature reached at both 3 vol. %
and 60 °C in the analysis of hydrogen
control to determine the capacity
and locations of PARs as a hydrogen
mitigation system [2]. Fifteen (15)
minutes of the start-up delay time are
assumed in severe accident analyses
while 12 hours of the start-up delay
time is assumed in design basis accident
analysis [12]. For new catalysts a
certain time is required until the flow
is fully developed by naural convection.
This time has been measured as
about 404 sec with a standard deviation
of 66.9 sec. As shown in Fig. 6,
the start-up delay times are well
within 15 minutes except the plants G
and H. The start-up delay times for
plant G and H1 show an average time
of 1,006 sec and 893 sec with a
standard deviation of 160 sec and
215 sec, respectively. The total averaged
start-up delay time for all plants
is estimated as 660.6 sec with a standard
deviation of 237.8 sec. For plants
C, D, F, H and M, the second tests does
not show a noticeable difference
compared to its first tests.
In the design basis accident such as
a loss-of-coolant-accident (LOCA),
the hydrogen is generated gradually
and the hydrogen concentration could
be reached at 4 vol. % after several
days without a hydrogen mitigation
system after a LOCA takes places. In
the analysis of hydrogen concentration
in the LOCA, twelve (12) hours of
the start-up delay time were assumed
after the hydrogen concentration and
the catalysts temperature reach at
both 3 vol. % and 60 °C. Although the
start-up delays of 12 hours are considered,
there is a sufficient margin to
maintain the hydrogen concentration
below the regulatory limit of 4 vol. %.
However, in the severe accident conditions,
the hydrogen concentration in
the containment abruptly increases at
the timing of the reactor vessel failure
so that the margin for start-up delay
for hydrogen removal may not be
sufficient compared to the situation of
a design basis accident. The regulatory
position in Korea is that the startup
delay times should be verified and
compared to the assumptions used in
the analysis of hydrogen control in
DBA and severe accident conditions.
In the case of plant G, H and N, the
analysis of hydrogen control in severe
accident conditions has been re-evaluated
with a longer delay time of
30 minutes in consideration of the
results of the start-up delay time
measurement tests in 2014. For the
Research and Innovation
Effects of Airborne Volatile Organic Compounds on the Performance of Pi/TiO 2 Coated Ceramic Honeycomb Type Passive Autocatalytic Recombiner ı Chang Hyun Kim, Je Joong Sung, Sang Jun Ha and Phil Won Seo