3. From the Ratings on pages 16 - 46:<br />
SELECT. YCAL0050 (Eng lish Units)<br />
53.1 Tons<br />
48.7 Compressor kW<br />
11.7 Unit EER<br />
4. Calculate Comp ressor kW at 50 Tons:<br />
kW = 50 x 48.7kW = 45.9kW<br />
53.1<br />
5. Calculate GPM:<br />
GPM = 50 Tons x 24 = 120 GPM<br />
10-F Range<br />
6. F ro m Page 14, read 10 ft of water cooler p ressure<br />
drop for GPM:<br />
7. AYCAL005O Is suitable.<br />
EXAMPLE -Brine Chilling<br />
1. GIVEN: Provide a capa city of 34 tons cooling<br />
30% by weight Ethylene Glycol from<br />
50-F td 401.0.0D025FF, 95-F air on<br />
the condenser, 60 Hz and 4000 IL altitude.<br />
2. DETERMINE:<br />
Unit Size<br />
kW Input<br />
Ethylene Glycol GPM<br />
Cooler Pressure D ro p<br />
3. See Ethylene Glycol correction factors, for 30% by<br />
weight Ethylene Glycol..<br />
12<br />
READ: .974 Tons factor<br />
.995 Compr. kW fa ctor<br />
26.1 GaIlF/ronsfactor<br />
4. See Performance Data Correc ti<br />
on Factors for<br />
0.00025 fouling factor and 4000 R alti tu<br />
de.<br />
READ: .083 Tons fa ctor<br />
. 1.021 kW factor<br />
RPP-24544 REV I<br />
S. From RATINGS on pages 16-46:<br />
145579-V--DS-12.1, AppendlxA<br />
Page 12 of 116<br />
SELECT. YCAL0040 (English Uras)<br />
36.1 Tons<br />
38.6 Compressor kW<br />
6. Detemime YCAL0040 b ri ne cooling capa city<br />
and Compressor kW requirement<br />
A Tons - 36.1 x .974 x .983 = 34.6<br />
S. Compr. kW - 38.6 x .995 x 1.021 = 39.2<br />
7. Determine average full load Comp ressor kW at<br />
34 tons:<br />
34 tons x (392 I(W) - 38.5 Compressor kW<br />
34.6 tons<br />
8. Determine Ethylene Glycol GPM:<br />
Tons x Gal. 71minribn factor<br />
GPM =<br />
Range<br />
GPM =<br />
34.0 x 26.1<br />
GPM = 88.7<br />
9. Determine Cooler Pressure Drop:<br />
/C- tee Ethylene Glycol cor rec ti on factors for<br />
30% by weight Ethylene Glycol.<br />
10<br />
READ: 1.096 Pressu re D ro p Factor<br />
B. See page 14 at 88.7 GPM for the YCAL0040.<br />
READ: 6.5 FL HO P ressure Drop<br />
C. Cooler Pressu re<br />
Drop = 6.5 x 1.096 or 7.1 FL<br />
H2O<br />
10. YCAL0040 Is suitable.<br />
^^w<br />
Originator.<br />
Attachment: 8 Date: 7L29LL O<br />
Calc. No: 145579-V-CA-004 Checked by.<br />
Rev. No.: 1 Date: D7 Nib. O q-<br />
Sheet 2 of 4<br />