3 Installation page 7<br />
3.2 Connection<br />
L1<br />
L2<br />
L3<br />
N<br />
PE<br />
L1 L2 L3<br />
EVG<br />
out1 out2<br />
lamp assembly<br />
earthed lead network side<br />
automatic cutout<br />
power choke<br />
cable shield<br />
lamp feeder cable<br />
Fig. 3: Power connection <strong>PE22</strong> / PE32<br />
Mains connection<br />
Fig. 4: Mains <strong>PE22</strong><br />
� <strong>PE22</strong>:<br />
<strong>ELC</strong> <strong>PE22</strong>_PE32-V2.2-09.11-GB Subject to technical alterations<br />
Fig. 3 shows the electrical installation.<br />
Operation of the ballasts requires a power<br />
choke in series (see technical data chapter<br />
6) in order to limit the total harmonic<br />
distortion of the line current to below 50%.<br />
The lamp feeder cable shielding must be<br />
connected to the <strong>ELC</strong>. To this end the<br />
connector has an EMC screw connection<br />
(also see: connection lamp cable).<br />
If wished, the shielding can also be<br />
connected to the lamp unit.<br />
The connection of mains supply cables and lamp feeder cables must be<br />
separated from control cables.<br />
Fig. 5: Mains PE32<br />
The cross section of the<br />
earthed wire must be at least<br />
10 mm².<br />
The three phases must be<br />
provided with an automatic<br />
cutout.<br />
In order to avoid damaging the terminal pins, please do not exceed the following<br />
torque:<br />
L1, L2, L3: 1,5 – 1,8 Nm<br />
Grounding conductor: 3,0 – 4,0 Nm<br />
PE32:<br />
L1, L2, L3: 1,5 – 1,8 Nm<br />
Grounding conductor: 1,5 – 1,8 Nm