3 Installation page 7<br />

3.2 Connection<br />

L1<br />

L2<br />

L3<br />

N<br />

PE<br />

L1 L2 L3<br />

EVG<br />

out1 out2<br />

lamp assembly<br />

earthed lead network side<br />

automatic cutout<br />

power choke<br />

cable shield<br />

lamp feeder cable<br />

Fig. 3: Power connection <strong>PE22</strong> / PE32<br />

Mains connection<br />

Fig. 4: Mains <strong>PE22</strong><br />

� <strong>PE22</strong>:<br />

<strong>ELC</strong> <strong>PE22</strong>_PE32-V2.2-09.11-GB Subject to technical alterations<br />

Fig. 3 shows the electrical installation.<br />

Operation of the ballasts requires a power<br />

choke in series (see technical data chapter<br />

6) in order to limit the total harmonic<br />

distortion of the line current to below 50%.<br />

The lamp feeder cable shielding must be<br />

connected to the <strong>ELC</strong>. To this end the<br />

connector has an EMC screw connection<br />

(also see: connection lamp cable).<br />

If wished, the shielding can also be<br />

connected to the lamp unit.<br />

The connection of mains supply cables and lamp feeder cables must be<br />

separated from control cables.<br />

Fig. 5: Mains PE32<br />

The cross section of the<br />

earthed wire must be at least<br />

10 mm².<br />

The three phases must be<br />

provided with an automatic<br />

cutout.<br />

In order to avoid damaging the terminal pins, please do not exceed the following<br />

torque:<br />

L1, L2, L3: 1,5 – 1,8 Nm<br />

Grounding conductor: 3,0 – 4,0 Nm<br />

PE32:<br />

L1, L2, L3: 1,5 – 1,8 Nm<br />

Grounding conductor: 1,5 – 1,8 Nm