5 Monitoring, warning, error, repair page 26<br />

Bit 0: The {Lamp Voltage Low}-bit is set if the burning voltage of the lamp falls<br />

below its minimum (set by the manufacturer). This bit will be reset if the lamp<br />

voltage exceeds the minimum.<br />

Bit 1: The {Run Up Long}-bit is set if the warm up of the lamp takes longer than<br />

expected. Reset occurs as soon as the {Start Lamp}-bit in register [Lamp<br />

Control] is set to 0 (the lamp being thus actively shut down by the operator<br />

via the PROFIBUS output data).<br />

Bit 4: The {Safety Relay Open} bit is set if the safety relay is not closed (e.g. on<br />

emergency shutdown). There are two different cases:<br />

• If in register [Lamp Control] {Start Lamp} bit is 0, the {Safety Relay<br />

Open} bit is automatically reset as soon as the safety relay is closed.<br />

• During lamp operation ({Start Lamp}=1 in [Lamp Control]) the {Safety<br />

Relay Open} bit remains set and the lamp will be shut down by the <strong>ELC</strong>.<br />

In this case {Safety Relay Open} will only be reset if {Start Lamp} in<br />

[Lamp Control] is reset and the safety relay has been closed.<br />

Bit 5: If the <strong>ELC</strong> cannot ignite the lamp the {Lamp Ignition Failed} bit will be set<br />

and remains in this status as long as {Start Lamp}=1 in [Lamp Control]. The<br />

{Lamp Ignition Failed} bit is reset as soon as {Start Lamp} in [Lamp<br />

Control] is reset.<br />

Bit 7: The {Init Signal Ok} bit reflects the status of the Init-Pin X1.1 of the<br />

initialisation signal (see paragraph 3.4.2).<br />

• {Init Signal Ok}=1 means 24 V on X1.1, the lamp may be ignited and<br />

operated normally.<br />

• {Init Signal Ok}=0 means 0 V on X1.1, the lamp cannot be operated.<br />

To render the <strong>ELC</strong> operational again in case {Init Signal Ok}=0 the<br />

initialisation signal on X1.1 has to be 24V and the start signal {Start Lamp}<br />

has to be reset.<br />

Bit 2, Bit 3 und Bit 6: {n/a} bits (not available) are reserved for future applications.<br />

<strong>ELC</strong> <strong>PE22</strong>_PE32-V2.2-09.11-GB Subject to technical alterations