EC2 – worked examples 4-1<br />
SECTION 4. <strong>WORKED</strong> <strong>EXAMPLES</strong> – DURABILITY<br />
EXAMPLE 4.1 [EC2 clause 4.4]<br />
Design the concrete cover of a reinforced concrete beam with exposure class XC1.<br />
The concrete in use has resistance class C25/30.<br />
Bottom longitudinal bars are 5φ 20; the stirrups are φ 8 at 100 mm.<br />
The max aggregate size is: dg = 20 mm (< 32 mm).<br />
The design working life of the structure is 50 years.<br />
Normal quality control is put in place.<br />
Refer to figure 4.1.<br />
Table of Content<br />
Fig. 4.1<br />
From table E.1N - EC2 we see that, in order to obtain an adequate concrete durability, the<br />
reference (min.) concrete strength class for exposure class XC1 is C20/25; the resistance<br />
class adopted (C25/30) is suitable as it is higher than the reference strength class.<br />
The structural class is S4.<br />
First, the concrete cover for the stirrups is calculated.<br />
With:<br />
cmin,b = 8 mm<br />
We obtain from table 4.4N - EC2:<br />
cmin,dur = 15 mm<br />
Moreover:<br />
Δcdur,γ = 0 ;<br />
Δcdur,st = 0 ;<br />
Δcdur,add = 0 .<br />
From relation (3.2):<br />
cmin = max (cmin,b; cmin,dur + Δcdur,γ - Δcdur,st - Δcdur,add; 10 mm) =<br />
max (8; 15 + 0 – 0 – 0; 10 mm) = 15 mm