EC2 – worked examples 4-1<br />

SECTION 4. <strong>WORKED</strong> <strong>EXAMPLES</strong> – DURABILITY<br />

EXAMPLE 4.1 [EC2 clause 4.4]<br />

Design the concrete cover of a reinforced concrete beam with exposure class XC1.<br />

The concrete in use has resistance class C25/30.<br />

Bottom longitudinal bars are 5φ 20; the stirrups are φ 8 at 100 mm.<br />

The max aggregate size is: dg = 20 mm (< 32 mm).<br />

The design working life of the structure is 50 years.<br />

Normal quality control is put in place.<br />

Refer to figure 4.1.<br />

Table of Content<br />

Fig. 4.1<br />

From table E.1N - EC2 we see that, in order to obtain an adequate concrete durability, the<br />

reference (min.) concrete strength class for exposure class XC1 is C20/25; the resistance<br />

class adopted (C25/30) is suitable as it is higher than the reference strength class.<br />

The structural class is S4.<br />

First, the concrete cover for the stirrups is calculated.<br />

With:<br />

cmin,b = 8 mm<br />

We obtain from table 4.4N - EC2:<br />

cmin,dur = 15 mm<br />

Moreover:<br />

Δcdur,γ = 0 ;<br />

Δcdur,st = 0 ;<br />

Δcdur,add = 0 .<br />

From relation (3.2):<br />

cmin = max (cmin,b; cmin,dur + Δcdur,γ - Δcdur,st - Δcdur,add; 10 mm) =<br />

max (8; 15 + 0 – 0 – 0; 10 mm) = 15 mm