CSE-Semaphore TWinSoft Manual - ioSelect
CSE-Semaphore TWinSoft Manual - ioSelect
CSE-Semaphore TWinSoft Manual - ioSelect
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Indirect (Ptr) = Bit the status of the digital Tag 'Bit' will be copied in the digital<br />
variable whose ModBus address is defined in the Tag or<br />
Constant 'Ptr'.<br />
Example:<br />
to write the status of dir0 in the output 'Q2' of the CPU (ModBus<br />
address 34):<br />
Indirect (34): dir0.<br />
A = indirect (Ptr) the Tag or Constant 'Ptr' contains the absolute ModBus address<br />
of the analog variable that will have its value assigned to the<br />
analog Tag 'A'<br />
Example:<br />
to read the value of the input 'ana1' of the CPU (ModBus address<br />
65):<br />
air0 = indirect (65).<br />
indirect (Ptr) = A the value of the analog Tag 'A' will be copied in the analog<br />
variable whose ModBus address is defined in the Tag or<br />
Constant 'Ptr'.<br />
Example:<br />
to write the value of ana0 of the CPU in the analog output: Rack<br />
1, Card 1, Channel 0 (ModBus address 288):<br />
Indirect (288) = ana0.<br />
<strong>TWinSoft</strong>: 8.32 – Getting Started 40