Section N- Main Control Box<br />

Power Panel— Until 3/05<br />

Fan Motor Contactors, Overloads and Fusing<br />

Components, Continued<br />

50 Horsepower Supply or Return Fan Motor- Code 22 or 32= S<br />

Across- The- Line Start (C10= AL)<br />

Sch. Part Part Voltage<br />

Sym.<br />

M9,10<br />

Description<br />

Contactors<br />

Number 208V 230V 380V 460V 575V<br />

4<br />

M19,20<br />

FB9,10<br />

Contactor- Supply (M9,10), Return (M19,20) Fan Motor<br />

Fuse Block and Fuses<br />

027514407 2 2 1 1 1<br />

4<br />

FB19,20 Fuse Block- Supply (FB9,10), Return (FB19,20) Fan Motor 023780213 2 3 2<br />

Fuse Block- Supply Fan Motor 023780212 1 1 1<br />

Fuse- FB9,10, 19, 20 025860518 6 3 6 3 3<br />

Fuse- FB9,10, 19, 20<br />

Overloads and Heaters<br />

025860416 3<br />

OL9,10 4<br />

OL19,20 Overload- Supply (OL9,10), Return (OL19,20) Fan Motor<br />

Until 1/98 030189400 2 2 1 1 1<br />

1/98 and later 059990301 2<br />

1/98 and later<br />

Overload Heater- OL9,10, 19, 20<br />

059990201 2 1 1 1<br />

Standard Efficiency Motor (C22/32= _AY or _GY) 023467200 2<br />

Standard Efficiency Motor (C22/32= _AY or _GY) 021858500 2 1 1<br />

Standard Efficiency Motor (C22/32= _AY or _GY)<br />

High or Prem.Eff. Motor (C22/32= _EY,_FY,_JY,_KY)<br />

023074800 1<br />

1<br />

1/98 and later 059990622 2<br />

1/98 and later 059990617 2 1 1<br />

1/98 and later<br />

LR10,20 Line Reactors<br />

059990616 1<br />

2<br />

NOTE: Quantities Listed are PER motor.<br />

1 For High Efficiency motors used on units built prior to 1/98, see the Overload Heater Chart at the end of this section (located on the<br />

page following the 50HP motors).<br />

2 When the unit has an inverter with bypass (C14= 1, 2, 3, 4, 5, 8) the line reactors are located in the bypass box. When there is no inverter<br />

bypass box the Line Reactors are located in the Main Control Power Panel. The Line Reactor part numbers are listed in Section F.<br />

3 This part number is used for a motor with no inverter. If the 208V unit has an inverter use fuse block p/n 023780218 and fuse p/n<br />

025860523.<br />

4 M9, M10, FB9 FB19, OL9 and OL19 are only used on 208/230V motors.<br />