EN<br />

5.9. Air cooling flow inlet<br />

Figure 9 Air cooling flow inlet<br />

Module Range Modules Typ 1 / 2 Typ 3 / 4<br />

Module Type 10 kW 20 KW<br />

Heat Dissipation with 100%<br />

Non-linear Load per Module<br />

( EN 62049-1-1:2003)<br />

Heat Dissipation with 100%<br />

Non-linear Load per Module<br />

( EN 62049-1-1:2003)<br />

Airflow (25 – 30°C) with<br />

Non-linear Load per Module<br />

(EN 620<strong>40</strong>-1-1:2003)<br />

1 module<br />

max<br />

2 modules<br />

max<br />

W 550 1100 550 - 1100 1100 - 2200<br />

BTU/h 1887 3754 1887 - 3754 3754 - 7508<br />

m 3 /h 150 150 150 300<br />

Dissipation at no load W 120 150 120 – 150 2<strong>40</strong> - 300<br />

www.rimatrix5.com<br />