Installation<br />
EN 6.6. Battery Connections<br />
6.6.1. Internal Battery Modules <strong>PMC</strong> <strong>40</strong><br />
In the <strong>PMC</strong> <strong>40</strong> Sub-rack there is space for up to 160 x 7Ah internal batteries. In the drawing below different<br />
Battery and System configurations are shown.<br />
NOTE:<br />
For UPS-Systems <strong>PMC</strong> <strong>40</strong> UPS-Module 10 kW, it is allowed to use 20-50 (only even numbers) of 12V-battery<br />
blocks depending the power sourced on the output<br />
For UPS-Systems <strong>PMC</strong> <strong>40</strong> UPS-Module 20 kW, it is allowed to use 30-50 (only even numbers) of 12V-battery<br />
blocks depending the power sourced on the output<br />
NOTE: Set-up the correct number of battery blocks on Control Panel (Menu: Service-Set-Up).<br />
<strong>PMC</strong> <strong>40</strong> TYP 1<br />
10x7Ah<br />
10x7Ah<br />
(1x<strong>40</strong>)x7Ah<br />
Module<br />
<strong>PMC</strong> <strong>40</strong> TYP 2<br />
10x7Ah<br />
10x7Ah<br />
10x7Ah<br />
10x7Ah<br />
10x7Ah<br />
Module Module<br />
10x7Ah<br />
10x7Ah<br />
10x7Ah<br />
10x7Ah<br />
10x7Ah<br />
10x7Ah<br />
(1x50)x7Ah (2x<strong>40</strong>)x7Ah<br />
10x7Ah<br />
10x7Ah<br />
www.rimatrix5.com<br />
User Guide <strong>PMC</strong> <strong>40</strong> Page 34/67<br />