EN<br />

Installation<br />

6. Installation<br />

!<br />

NOTE!<br />

For the assembling instructions of the <strong>PMC</strong><strong>40</strong> please have a look on the<br />

appendix of this manual, page XX<br />

The customer has to supply the wiring to connect the UPS to the local power source. The electrical installation<br />

procedure is described in the following text. The installation inspection and initial start up of the UPS and extra<br />

battery cabinet must be carried out by a qualified service personnel such as a licensed service engineer from<br />

the manufacturer or from an agent authorized by the manufacturer.<br />

WARNING!<br />

WARNING!<br />

The instruction in this user manual have always to be followed in order to<br />

avoid injuries from electrical impacts.<br />

ALL THE OPERATIONS IN THIS MANUAL MUST BE PERFORMED BY<br />

AUTHORISED ELECTRICIANS OR BY QUALIFIED INTERNAL<br />

PERSONNEL.<br />

DO NOT OPERATE IN CASE OF PRESENCE OF WATER OR MOISTURE.<br />

BY OPENING OR REMOVING THE UPS-COVERS YOU RUN RISK OF<br />

EXPOSURE TO DANGEROUS VOLTAGES.<br />

Physical injury or death may follow, or damage may occur to the UPS, or the<br />

load equipment if these instructions are ignored.<br />

To ensure correct operation of the UPS and its ancillary equipment it is necessary to provide the mains cables<br />

with appropriate fuse protection.<br />

The UPS unit has the following power connections:<br />

Rectifier (In) : Three-phase (1L1, 1L2, 1L3), Neutral (1N) and protective earth (PE)<br />

connection for the rectifier input<br />

Bypass (In) : Three-phase (2L1, 2L2, 2L3), Neutral (2N)<br />

connection for the bypass if used as Dual Feed input<br />

Load (Out) : Three-phase (3L1, 3L2, 3L3), Neutral (3N) and protective earth (PE)<br />

connection for the load output<br />

External Battery : Plus (+), Common (N), Minus (-) and protective earth (PE)<br />

connection for the external batteries<br />

Figure 11 Connection Scheme<br />

UPS<br />

0V 230V<br />

www.rimatrix5.com<br />

User Guide <strong>PMC</strong> <strong>40</strong> Page 22/67<br />