Safety<br />
2.2. User safety measures<br />
The only permitted operator functions:<br />
• Use of the LCD control panel and the manual bypass<br />
• Switching the UPS system on and off using the control panel (not, however, commissioning)<br />
• Operation of additional communications interfaces<br />
• SNMP adaptors and their software<br />
• Modem/GSM or modem/Ethernet adaptors and their software<br />
• Multidrop kit for the parallel switching of the communications information between multiple enclosures<br />
The user must observe the safety measures and may perform only described operating commands. The user<br />
must also follow the instructions contained in these operating instructions. Any non-observance of or deviation<br />
from the instructions can cause danger for the user or even the loss of the load.<br />
Danger!<br />
The removal of screws or the covers of the UPS system or the battery rack is prohibited. There<br />
is danger of electrical shock!<br />
Warning<br />
Large leakage current: Prior to connecting the UPS system, ensure that the system is earthed!<br />
Danger!<br />
The user must provide all input switches of the system with warning signs. The maintenance<br />
personnel must be warned about dangerous voltages. The control panel must be given the<br />
following text: "Before beginning any maintenance work on switches, ensure that the UPS<br />
system is insulated."<br />
2.3. Environmental Considerations<br />
The UPS must be installed according to the recommendations in this manual. To operate the UPS at peak<br />
efficiency, your installation site should meet the environmental parameters outlined in this manual. Excessive<br />
amount of dust in the operating environment of the UPS may cause damage or lead to malfunction. The UPS<br />
should be always protected from the outside weather and sunshine. If you intend to operate the system at an<br />
altitude higher than 1000 meters, contact your local sales or service office for important information about high<br />
altitude operation. The operating environment must meet the weight, airflow, size and clearance requirements<br />
specified in the technical datasheet.<br />
Under no circumstances the UPS should be installed in an airtight room, in the presence of flammable gases, or<br />
in an environment exceeding the specification.<br />
The basic environmental requirements of the UPS system are:<br />
• Ambient Temperature Range: 0 to +<strong>40</strong>˚C (32 – 104˚F )<br />
• Recommended Operating Range: +20 to +25˚C (68 – 77˚ F)<br />
• Maximum Relative Humidity: 95% (non-condensing)<br />
The UPS cabinet uses forced air cooling to regulate internal component temperature. Air inlets are in the<br />
bottom sides and front of the cabinet, and outlets in the rear of the cabinet. You must allow clearance in back of<br />
the cabinet for proper air circulation.<br />