5.1 Safety distances.<br />
Units call in mm (inches)<br />
Type Arc chute Main- Additional Deflector Safety distances / Insulated plates Safety distances / Earthed plates<br />
Gerapid Connection isolation<br />
E A B C D A B C D<br />
2607 / 4207 1x2 all 10 (0,4) 700 (27,6) 150 (5,9) 150 (5,9) 120 (4,7) 1000 (39,4) 300 (11,8) 300 (11,8) 300 (11,8)<br />
1x3 all 1) 1) 1) 1) 1) - - - -<br />
1x4 all 150 (5,9) 700 (27,6) 150 (5,9) 150 (5,9) 120 (4,7) 1350 (53,2) 450 (17,7) 450 (17,7) 200 (7,9)<br />
2x2 all 80 (3,15) 1000 (39,4) 180 (7,1) 180 (7,1) 180 (7,1) 1350 (53,2) 450 (17,7) 450 (17,7) 300 (11,8)<br />
2x3 all 80 (3,15) 1000 (39,4) 180 (7,1) 180 (7,1) 180 (7,1) - - - -<br />
2x4 H / H Plate 150 (5,9) 1000 (39,4) 180 (7,1) 180 (7,1) 180 (7,1) - - - -<br />
2x4 H / H Sidewalls 150 (5,9) 1000 (39,4) 180 (7,1) 180 (7,1) 180 (7,1) - - - -<br />
2x4 SEL / H Pan 150 (5,9) 1000 (39,4) 180 (7,1) 180 (7,1) 180 (7,1) - - - -<br />
6007 1x2 V / V Heat sink 10 (0,4) 1000 (39,4) 300 (11,8) 300 (11,8) 180 (7,1) - - - -<br />
1x3 1) 1) 1) 1) 1) 1) 1) - - - -<br />
1x4 V / V Heat sink 150 (5,9) 1000 (39,4) 300 (11,8) 300 (11,8) 180 (7,1) - - - -<br />
2x2 V / V Heat sink 80 (3,15) 1000 (39,4) 180 (7,1) 180 (7,1) 180 (7,1) - - - -<br />
2x3 V / V Heat sink 80 (3,15) 1000 (39,4) 180 (7,1) 180 (7,1) 180 (7,1) - - - -<br />
2x4 1) 1) 1) 1) 1) 1) 1) - - - -<br />
8007 1x2 V / V Heat sink 10 (0,4) 1000 (39,4) 300 (11,8) 300 (11,8) 180 (7,1) - - - -<br />
1x3 1) 1) 1) 1) 1) 1) 1) - - - -<br />
1x4 1) 1) 1) 1) 1) 1) 1) - - - -<br />
2) 2x2 V / V Heat sink 80 (3,15) 1000 (39,4) 180 (7,1) 180 (7,1) 180 (7,1) - - - -<br />
2) 2x3 V / V Heat sink 80 (3,15) 1000 (39,4) 180 (7,1) 180 (7,1) 300 (11,8) - - - -<br />
2x4 1) 1) 1) 1) 1) 1) 1) - - - -<br />
1) will be checked by customers order 2) acc. IEC 947-2 / ks-setting