7.2.3 Example of order no. 3<br />
Customer wants to use Gerapid as a field discharge breaker to commutate current<br />
from excitation system of synchronous machine to the discharge resistor circuit.<br />
Customer has previously tested one Gerapid breaker in a special test sequence using<br />
special ratings and internal standard “XXX 123”. Customer requests to put on the<br />
nameplate rated parameters that have been tested. After agreement with <strong>GE</strong> both<br />
parties decided to create special version of the breaker and assign to it a letter “a” as<br />
extension of standard name. These breakers will be a retrofit units replacing old<br />
Gearapid SE type.<br />
1 Load current of 3200 A;<br />
2 Operating voltage of 2750 V;<br />
3 High power, low stability, source 220 V AC available for closing solenoid;<br />
4 Terminals suitable to install SEL current measurement system.<br />
5 Plus pole connected to the TOP terminal;<br />
6 With SEL measurement system;<br />
7 Without OC release;<br />
8 Low power, high stability, 24 V DC source available for control supply;<br />
9 With maximum possible number of auxiliary contacts.<br />
10 Without OC trip target;<br />
11 Zero voltage release;<br />
12 With ED impulse release supply directly from external C-bank;<br />
13 Without forced tripping release;<br />
14 With contacts’ position indicator;<br />
15 With side insulation panels;<br />
16 With hand lever;<br />
17 Without arc chute indicator;<br />
18 Counter not available;<br />
19 Special retrofit connectors for Gearapid SE breakers;<br />
20 According to IEC 60947-2 standard.<br />
21 User Manual must be in Polish.<br />
Correct catalogue code shall be: 2 a 5 R 5 1 2 0 1 4 0 6 1 0 1 1 1 0 0 3 4<br />
General remarks:<br />
Customer’s special solution with non-typical ratings. Additional letter “a” will be<br />
assign to this configuration exclusively. Later customer can use this letter to call<br />
the same configuration.<br />
It is possible to supply closing drive and controls from two separate source of<br />
power.<br />
2012-11-21 S47183R01E06 Design and specifications are subject to change without notice 55