A-1<br />
INSTALLATION<br />
TECHNICAL SPECIFICATIONS – <strong>DC</strong>-<strong>600</strong><br />
Standard<br />
Volatge<br />
INPUT - THREE PHASE ONLY<br />
Input Current at Rated Output<br />
100% Duty Cycle 60% Duty Cycle 50% Duty Cycle<br />
Code<br />
Number<br />
A-1<br />
230/460/575/60<br />
108/54/43<br />
122/61/49<br />
134/67/54<br />
10650<br />
Duty Cycle<br />
100% Duty Cycle<br />
60% Duty Cycle<br />
50% Duty Cycle<br />
Output Range<br />
70A/13V-780A/44V (CV)<br />
90A/24V-780A/44V (CC)<br />
INPUT<br />
VOLTAGE /<br />
FREQUENCY<br />
230<br />
460<br />
575<br />
RATED OUTPUT<br />
Amps<br />
<strong>600</strong><br />
680<br />
750<br />
OUTPUT<br />
Maximum Open Circuit Voltage<br />
72V<br />
Volts at Rated Amperes<br />
44<br />
44<br />
44<br />
Auxiliary Power<br />
See the OPERATION section<br />
for Auxiliary Power<br />
information by model<br />
RECOMMENDED INPUT WIRE AND FUSE SIZES<br />
HERTZ INPUT AMPERE TYPE 75°C TYPE 75°C<br />
RATING ON COPPER WIRE GROUND WIRE<br />
NAMEPLATE IN CONDUIT IN CONDUIT<br />
AWG(IEC-MM 2 ) SIZES AWG(IEC-MM 2 ) SIZES<br />
30°C (86°F) Ambient<br />
60<br />
108<br />
2 (34)<br />
6 (14)<br />
60<br />
54<br />
6 (14)<br />
8 (8.4)<br />
60<br />
43<br />
8 (8.4)<br />
8 (8.4)<br />
TYPE 75°C<br />
(SUPER LAG)<br />
OR BREAKER<br />
SIZE (AMPS) 1<br />
175 Amp<br />
90 Amp<br />
70 Amp<br />
HEIGHT<br />
30.75 in<br />
781 mm<br />
PHYSICAL DIMENSIONS<br />
WIDTH<br />
22.25 in<br />
567 mm<br />
DEPTH<br />
39.0 in<br />
988 mm<br />
WEIGHT<br />
522 lbs.<br />
237 kg.<br />
1 Also called “inverse time” or “thermal/magnetic” circuit breakers; circuit breakers which have a delay in tripping action that decreases as the magnitude of the current increases.<br />
<strong>DC</strong>-<strong>600</strong>