TXAEY 133<br />

technical data<br />

Table “ A”: Technical data<br />

TXAEY model 133<br />

Cooling operation in AUTOMATIC 1 mode<br />

Nominal cooling c apacit y (*) kW 34, 00<br />

E.E.R. (*) 2,56<br />

E.S.E.E.R. (*) 2,84<br />

Cooling operation with heat recovery in AUTOMATIC 2 mode<br />

Nominal cooling c apacit y in mai n heat exchanger (**) kW 32, 40<br />

Nominal heating capacit y in s econdar y heat exc hanger (**) kW 44, 20<br />

C.O.P. (**) 6,25<br />

Heat pump operation in modes SELECT 1-2 / AUTOMATIC 3<br />

Nominal heating capacity (***) kW 39, 14<br />

C.O.P. (***) 2,94<br />

Sound pressure (****) dB(A) 54<br />

Sound power (*****) dB(A) 78<br />

Scroll/step compress or No. 1/1<br />

Circuits No. 1<br />

Fans No. x kW 1 x 0 .61<br />

Main exchanger nominal flow (*) l/h 5846<br />

Nominal press ure drops in main exchanger (*) kPa 32<br />

Nominal press ure drops in main exchanger (**) kPa 42<br />

Water content in main exchanger l 3,20<br />

Residual s tatic pressure at the main heat exchanger (*) P1/ P2 kPa 134 / 230<br />

Residual s tatic pressure at the main heat exchanger (*) ASP1/ASP2 kPa 102 / 198<br />

Tank water content ASP1 / ASP2 l 80 / 80<br />

Main/secondary recovery exchanger nominal flow rate (***) l/h 7602<br />

Secondary r ecover y exchanger pr essure drops (***) kP a 53<br />

Recovery exchanger water content l 3,20<br />

R410A refrigerant c harge<br />

See s erial No. plat e<br />

Pol yest er oil charge<br />

See c ompress or plat e<br />

(*) In the f ollowi ng conditions : condenser<br />

input air temperat ure 35°C; c hilled water<br />

temperature 7°C; mai n heat exchanger<br />

(evapor ator) temperat ure differential 5°C.<br />

(**) In the following conditions: chilled water<br />

temperature 7°C; t emper ature diff erenti al at<br />

main exchanger (evaporator) 5°C, sec ondar y<br />

exchanger (recovery) hot water outlet<br />

temperature 40/ 45°C at nominal flow.<br />

N.B.:<br />

The val ues for available static press ure of<br />

the pumps and t he press ure drops of t he<br />

exc hangers can be found on page 39.<br />

The calc ulation of t he E.E.R. and C.O .P.<br />

does not t ake t he pump absorption i nto<br />

account.<br />

H<br />

(***) In the following conditions: coil inlet air<br />

temperature 7°C D.B., 85% R.H.; main<br />

exc hanger (condens er/evaporator) or<br />

secondary exchanger (recovery) hot water<br />

outlet temperat ure 40/ 45°C at nominal flow.<br />

(****) Level of s ound pressure in dB(A)<br />

measured at a distance of 5 m from t he unit<br />

with a directionalit y fac tor of 2 (to obt ain t he<br />

val ue i n open space, subtract 3 dB(A)).<br />

(*****) Sound power level in dB (A) bas ed on<br />

measurements made i n acc ordance wit h t he<br />

UNI EN-ISO 3744 standard and Eurovent<br />

8/1.<br />

P<br />

L<br />

19