<strong>TCAEY</strong>-<strong>THAEY</strong> 115÷238<br />

construction features<br />

<strong>TCAEY</strong>-<strong>THAEY</strong> 115÷238models<br />

Construction features<br />

Standard installation<br />

○ Load-bearing structure and panels in<br />

galvanised and painted sheet steel (RAL 9018);<br />

base in gal vanised s heet s teel.<br />

○ Hermetic, Scroll-type rotar y compressors,<br />

complete wit h internal thermal prot ection and<br />

crankcase heat er (for models 127÷238)<br />

activat ed aut omaticall y when the unit st ops (as<br />

long as t he power s uppl y to the unit is<br />

preser ved).<br />

○ Wat er side, braz e welded plat e heat<br />

exchanger in stainless steel, compl ete with<br />

antifreeze electric heat er and s uitabl y insul ated.<br />

○ Air side heat exc hanger c omprised of a coil<br />

of copper pipes and aluminium fi ns.<br />

○ Double electric axial fan with ext ernal rotor,<br />

equipped with inter nal t her mal pr otecti on and<br />

complete with protection grille for models<br />

115÷130, 238 and indi vidual f an for models<br />

133-233.<br />

○ Male threaded water c onnections.<br />

○ Differential pressur e s witch t hat protects the<br />

unit from any i nterruptions to the water flow.<br />

○ Refrigerant circuit made from annealed<br />

copper pipi ng (EN 12735-1-2) complete wit h:<br />

drier filter, charge connecti ons, saf et y pressure<br />

switch on the high pressure side, press ure<br />

switch on the low pressure si de, safety valve<br />

(for models 127÷238), thermos tatic expansion<br />

val ve ( 2 for <strong>THAEY</strong>, 3 for models 133-238),<br />

cycle i nversion val ve (for <strong>THAEY</strong>), liquid<br />

receiver (for <strong>THAEY</strong>) and chec k valves (2 for<br />

<strong>THAEY</strong>), and gas s eparator (for models 133-<br />

238).<br />

○ Unit wit h IP24 level of protec tion.<br />

○ Possibility to select two controls:<br />

• STANDARD, with Adaptive Function;<br />

• compati ble with Adaptive<br />

Function Plus.<br />

○ The unit is complete with the R410A<br />

refrigerant charge.<br />

Potential installations<br />

Standard – Installation without pump (onl y<br />

availabl e for models 133, 233 and 238).<br />

Pump P1 – I nstallation wit h pump.<br />

Pump P2 – I nstallation wit h increased st atic<br />

pressure pump (onl y availabl e f or models 133,<br />

233 and 238) (availabl e as a f act ory fitted<br />

accessor y).<br />

Tank & Pump ASP1 – I nstallation wit h pump<br />

and water buf fer t ank. The inertial water buf fer<br />

tank is i nstalled on t he water circuit deli ver y<br />

pipe.<br />

Tank & Pump ASP2 – I nstallation wit h<br />

increased st atic press ure pump and wat er<br />

buff er tank (only available for models 133, 233<br />

and 238) (available as a fac tor y fitt ed<br />

accessor y). The inertial water buffer tank is<br />

installed on the wat er circuit deliver y pipe.<br />

Electrical panel<br />

Option with STANDARD control<br />

○ Electrical board accessibl e by openi ng the<br />

front panel, c onf orming with c urrent IEC<br />

standards, and whic h can be opened and<br />

closed wit h a s uitable t ool.<br />

○ Compl ete with:<br />

• electrical wiring arranged f or power suppl y<br />

400-3ph+N-50Hz;<br />

• auxiliary power supply 230V-1ph-50Hz<br />

drawn from t he main power s upply;<br />

• general isolator, c omplet e with door<br />

interloc king isolat or;<br />

• aut omatic compr essor protecti on s witc h;<br />

• protection fuse for auxiliar y circuit;<br />

• compressor power contactor;<br />

• anti-distur banc e net wor k filter;<br />

• compressor pr otecti on phase s equence<br />

monitor;<br />

• unit protec tion against l ac k of a power<br />

suppl y phase;<br />

• transfor mer f or elec tronic c ontrol;<br />

• user int erface ter minal board;<br />

• remot e unit c ontrol.<br />

○ Programmable elec tronic boar d with<br />

microproc essor, c ontrolled by the keypad<br />

inserted in t he machine.<br />

○ This electronic board performs t he following<br />

functi ons:<br />

• Regulation and management of t he inl et<br />

wat er temperat ure s et points ; of c ycle reversal<br />

(<strong>THAEY</strong>); of the safety ti mer delays ; of the<br />

circulating pump; of the compr essor and s ystem<br />

pump hour-run meter; of temperat ure defrost<br />

cycles (<strong>THAEY</strong>); of the electronic anti-freeze<br />

protecti on which cuts in aut omatic ally when the<br />

mac hine is s witc hed of f; and of the f uncti ons<br />

which control t he operation of the indi vidual<br />

parts making up t he machine;<br />

• complete protection of the unit, automatic<br />

emergenc y shutdown and dis play of t he alarms<br />

which have been acti vat ed;<br />

• visual indic ation of the pr ogrammed set<br />

points via t he display; of the in/ out wat er<br />

temperature vi a the display; of the alar ms via<br />

the display; and of c ooling/heat-pump operating<br />

mode via led (<strong>THAEY</strong>);<br />

• self-diagnosis with continuous monit oring of<br />

the func tioni ng of t he unit ;<br />

• user int erface menu;<br />

• alarm c ode and descripti on;<br />

○ Advanced functions:<br />

• set up for serial connection (KIS and<br />

KRS232/KUSB acc essor y);<br />

• chec k-up and monitoring of scheduled<br />

maintenanc e st atus ;<br />

• testing of the units assisted by computer;<br />

• self-diagnosis with continuous monit oring of<br />

the func tioni ng of t he unit ;<br />

• with Ad aptive Fun ction.<br />

Option with compatible<br />

control<br />

○ Electrical board accessibl e by openi ng the<br />

front panel, c onf orming with c urrent IEC<br />

standards, and whic h can be opened and<br />

closed wit h a s uitable t ool.<br />

○ Compl ete with:<br />

• electrical wiring arranged f or power suppl y<br />

400-3ph+N-50Hz;<br />

• auxiliary power supply 230V-1ph-50Hz<br />

drawn from t he main power s upply;<br />

• general isolator, c omplet e with door<br />

interloc king isolat or;<br />

• aut omatic compr essor protecti on s witc h;<br />

• protection fuse for auxiliar y circuit;<br />

• compressor power contactor;<br />

• remot e unit c ontrol.<br />

○ Programmable elec tronic boar d with<br />

microproc essor, c ontrolled by the keypad<br />

inserted in t he machine.<br />

○ This electronic board performs t he following<br />

functi ons:<br />

• Regulation and management of t he outl et<br />

wat er temperat ure s et points ; of c ycle reversal<br />

(<strong>THAEY</strong>); of the safety ti mer delays ; of the<br />

circulating pump; of the compr essor and s ystem<br />

pump hour-run meter; of the el ectronic antifreeze<br />

prot ection which c uts i n automaticall y<br />

when the machine is s witched off ; and of the<br />

functi ons whic h control t he operation of t he<br />

indivi dual parts making up the mac hine;<br />

• complete protection of the unit, automatic<br />

emergenc y shutdown and dis play of t he alarms<br />

which have been acti vat ed;<br />

• compressor pr otecti on phase s equence<br />

monitor;<br />

• unit protec tion against l ow or high phase<br />

power suppl y voltage;<br />

• visual indic ation of the pr ogrammed set<br />

points on the dis play; of the inlet /outlet water<br />

temperature vi a the display; of the alar ms via<br />

the display; and of c ooling/heat-pump operating<br />

mode via LEDs (for <strong>THAEY</strong> models);<br />

• self-diagnosis with continuous monit oring of<br />

the func tioni ng of t he unit ;<br />

• user int erface menu;<br />

• alarm c ode and descripti on;<br />

• alarm histor y management (menu<br />

protect ed by manuf act urer password).<br />

○ The f ollowi ng is memorised f or each alarm:<br />

• dat e and time of inter venti on (if t he KSC<br />

accessor y is present);<br />

• alarm c ode and descripti on;<br />

• inlet/outlet wat er temperatur es when t he<br />

alarm inter vened;<br />

• alarm delay time from t he s witc h-on of the<br />

connected device;<br />

• compressor st atus at moment of alarm;<br />

○ Advanced functions:<br />

• configured for s erial connec tion (KR S485,<br />

KFTT10, KRS232 and KUSB acc essor y);<br />

• possibility to have a digital input for remote<br />

management of the double s et point (contact<br />

RHOSS S.p.A. pre-sales ).<br />

• possibility to have an analogue input for the<br />

scrolling set-point via a 4-20mA remote signal<br />

(contact RHOSS S.p.A. pre-sales );<br />

• configured for management of ti me bands<br />

and operation parameters with the possibility of<br />

daily/weekl y operating programs (KSC<br />

accessor y);<br />

• chec k-up and monitoring of scheduled<br />

maintenanc e st atus ;<br />

• testing of the units assisted by computer;<br />

• self-diagnosis with continuous monit oring of<br />

the func tioni ng of t he unit .<br />

○ Set-point regulation via t he<br />

AdaptiveFunction Plu s with two options:<br />

• fixed s et-poi nt (Pr eci sion options);<br />

• scrolling set-point (Economy opti on).<br />