TCAEY-THAEY 115÷238 - Rhoss
TCAEY-THAEY 115÷238 - Rhoss
TCAEY-THAEY 115÷238 - Rhoss
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
0 OFF<br />
I ON<br />
TXAEY 117÷130<br />
dimensions and footprints<br />
TXAEY 117÷130 dimensions and footprints, P1 installation<br />
o<br />
p<br />
a<br />
c<br />
6<br />
2<br />
3<br />
1<br />
8<br />
11<br />
12 11<br />
6<br />
4<br />
e<br />
10<br />
9<br />
n<br />
m<br />
13 14<br />
15 16<br />
17<br />
5<br />
i<br />
l<br />
i<br />
7 b<br />
7<br />
f<br />
d g h<br />
g<br />
Model a b c d e f g h i l m n o p<br />
117 mm 1490 1522 500 580 1090 60 20 1448 82 340 150 160 60 100<br />
124 mm 1490 1522 500 600 1280 60 20 1448 82 340 150 160 60 100<br />
130 mm 1790 1822 600 695 1510 60 20 1748 82 440 150 160 60 100<br />
1. Control panel;<br />
2. Isolat or;<br />
3. Electrical board;<br />
4. Compressor;<br />
5. Pump;<br />
6. Fan;<br />
7. Anti-vi bration support (KSA acc essor y);<br />
8. Coil;<br />
9. Protecti on mes h (KRP access ory);<br />
10. Expansion vessel;<br />
11. Power suppl y inl et;<br />
12. Pressure gauge<br />
13. Primar y wat er outlet;<br />
14. Recover y water outlet;<br />
15. Primar y water inlet;<br />
16. Recover y water inlet;<br />
17. Condensation drain.<br />
Installation<br />
○ The unit is designed for outdoor inst allation.<br />
○ The unit is equipped wit h male threaded water connections.<br />
○ The unit must be positioned to c ompl y with the mi nimum<br />
recommended cl earances, bearing in mind the acc ess t o wat er and<br />
electrical connections .<br />
○ The unit c an be equipped wit h anti- vibration mountings on request<br />
(KSA).<br />
○ We recommend installing intercept valves that isolate the unit fr om<br />
the res t of the s yst em.<br />
○ It is ess ential to fit a metal mes h filter (squar e mesh of no greater<br />
than 0. 8 mm) on the unit ret urn piping.<br />
○ The unit may not be inst alled on brac kets or shel ves.<br />
○ Correct installation and positioning includes levelling the unit on a<br />
surface c apable of bearing its weight.<br />
L4<br />
Clearances and positioning<br />
L3<br />
L1<br />
Model 117 124 130<br />
L1 mm 300 300 400<br />
L2 mm 600 600 600<br />
L3 mm with open outlet<br />
L4 mm 300 300 300<br />
Movement<br />
○ The unit s houl d be handled with c are, in order to avoi d damage t o<br />
the exter nal struc ture and t o t he internal mechanical and el ectrical<br />
components.<br />
○ Do not stack the units.<br />
○ The t emperature li mits for s torage are -9° ÷45°C.<br />
L2<br />
Weights<br />
Model 117 124 130<br />
TXAEY kg 220 280 370<br />
The weights refer t o pac kaged units without water.<br />
The weight of t he full unit is obt ained by adding t o t he weight of the tank<br />
wat er contents, i ndicated in t abl e “A”.<br />
46