<strong>Operating</strong> <strong>Instructions</strong> <strong>Safety</strong> <strong>Switch</strong> <strong>CET</strong>.-<strong>AR</strong>-...-<strong>CH</strong>-...<br />
Always use input RST in series connections. All switches in a chain can be reset at<br />
the same time with this reset input. To do this, a voltage of 24 V must be applied<br />
to the RST input for at least 3 seconds. If input RST is not used in your application,<br />
it should be connected to 0 V.<br />
Note the following on this aspect:<br />
ÌÌA common signal must be used for all switches in the chain. This can be a<br />
changeover switch or the output of a control system. A button is not suitable<br />
because Reset must always be connected to GND during operation (see switch<br />
S11 in Figure 12).<br />
ÌÌReset must always be performed simultaneously for all switches of the chain.<br />
Information on operation in a mixed <strong>AR</strong> switch chain<br />
The safety switch <strong>CET</strong>-<strong>AR</strong> has a longer risk time than a CES-<strong>AR</strong> switch (see section<br />
Technical data and Typical system times).<br />