<strong>Operating</strong> <strong>Instructions</strong> <strong>Safety</strong> <strong>Switch</strong> <strong>CET</strong>.-<strong>AR</strong>-...-<strong>CH</strong>-...<br />

Always use input RST in series connections. All switches in a chain can be reset at<br />

the same time with this reset input. To do this, a voltage of 24 V must be applied<br />

to the RST input for at least 3 seconds. If input RST is not used in your application,<br />

it should be connected to 0 V.<br />

Note the following on this aspect:<br />

ÌÌA common signal must be used for all switches in the chain. This can be a<br />

changeover switch or the output of a control system. A button is not suitable<br />

because Reset must always be connected to GND during operation (see switch<br />

S11 in Figure 12).<br />

ÌÌReset must always be performed simultaneously for all switches of the chain.<br />

Information on operation in a mixed <strong>AR</strong> switch chain<br />

The safety switch <strong>CET</strong>-<strong>AR</strong> has a longer risk time than a CES-<strong>AR</strong> switch (see section<br />

Technical data and Typical system times).<br />

29