Typical system times<br />
The specified times are maximum values for <strong>AR</strong> switch chains with 20 devices.<br />
Individual devices have shorter system times.<br />
Ready delay: After switching on, the unit carries out a self-test for 8 s. The system<br />
is ready for operation only after this time.<br />
<strong>Switch</strong>-on time of safety outputs: The max. reaction time from the moment<br />
when the safety guard is locked to the moment when the safety outputs switch<br />
on T on<br />
is 400 ms.<br />
Simultaneity monitoring, safety inputs IA/IB: If the safety inputs have different<br />
switching states for longer than 150 ms, the safety outputs OA/OB will be switched<br />
off. The devices switches to fault state.<br />
Risk time according to EN 60947-5-3: If an actuator moves outside the operating<br />
distance, the safety outputs OA and OB are deactivated after a maximum<br />
of 500 ms.<br />
Difference time: The safety outputs OA and OB switch with a slight time offset.<br />
They have the same signal state at the latest after a difference time of 10 ms.<br />
Clock pulses at the safety outputs: The device generates its own clock signal<br />
on the output lines OA/OB. A downstream control system must tolerate these<br />
pulses, which may have a length of up to 1 ms.<br />
This can usually be set up in the control systems by parameter assignment. If<br />
parameter assignment is not possible for your control system or if shorter clock<br />
pulses are required, please contact our support organization.<br />
The pulses are also output when the safety outputs are switched off.<br />
39