5. Control <strong>system</strong><br />

If a buffer sensor T5 is available as an option for the<br />

activation of the reheating function and its temperature<br />

is less than the circulation temperature + 2K, the<br />

circulation is then discontinued.<br />

As a result of the reheating function it is to be assumed<br />

that after reheating and for a conceivable period of<br />

time thereafter sufficient temperature is available in the<br />

buffer.<br />

Outside the active time slot, the circulation is always<br />

in the “pulse generated” mode, i.e. always when a<br />

drawing off of approx. 1 s has been carried out, the<br />

circulation pump is switched on for the programmed<br />

time in “circulation-running time” and the circulation is<br />

then also blocked from being reactivated for the preset<br />

“circulation-rest time” period.<br />

Circulation running time = 300 s<br />

From 0 – 600 s adjustable running time of the circulation<br />

pump.<br />

Circulation rest time = 5 min<br />

From 0 – 120 min adjustable blocking time for<br />

reactivating the circulation.<br />

Circulation hot water set value = 40°C<br />

From 10°C to 50°C adjustable temperature for circulation<br />

in the time slot.<br />

Sensor TF3 = select sensor T3 or T6 (optional)<br />

In the factory setting T3 is used for measuring the<br />

circulation temperature. However, an independent<br />

sensor T6 (optional) can also be used directly in the<br />

circulation pipes for this purpose.<br />

Option T5: With an additional sensor T5 (optional),<br />

which is installed in the buffer, two further functions<br />

can be activated.<br />

■ Activation T5<br />

If the activation T5 = on is selected, it is possible to<br />

only put the control <strong>system</strong> into operation after a<br />

specified buffer temperature has been attained.<br />

Factory setting = off<br />

Switch-on temperature = 35°C temperature<br />

(adjustment range 35°C to 55°C)<br />

Hysteresis = 3 K<br />

(adjustment range 3 K to 10 K)<br />

■ Reheating ON/OFF<br />

Optionally the additional „reheating” function can be<br />

activated. When there is a deviation lower than an<br />

adjustable set value for the buffer, this function is an<br />

external heat source which is activated to reheat<br />

the buffer until it reaches the set level.<br />

The requirement for this is that the heat source is<br />

actually able to supply the desired temperature level.<br />

For this purpose the contact S1 on the controller<br />

circuit board is used. This contact can be charged<br />

with 4 A 230 V AC. The set value for the storage<br />

temperature can be defined as an absolute value<br />

(fixed value e.g.: 65°C) or as a relative value.<br />

10<br />

Should the relative value be used, the set value for<br />

the buffer temperature is calculated from the<br />

programmed hot water – set temperature + the<br />

entered value for the „splay”. e.g.: hot water set<br />

temperature 50°C + splay 20 K = 70°C buffer<br />

temperature. Should the programmed or calculated<br />

set value deviate lower by 3 K, the external heat<br />

source is kept activated until the set value is reached<br />

again. The temperature values needed for this can be<br />

set in the programming menu, under the submenu<br />

“reheating”. (See 5.3.3)<br />

■ Pre-mixer ON/OFF<br />

As a rule, this selection is not active in this control<br />

<strong>system</strong>!<br />

■ Disinfection<br />

The “disinfection” function can be activated in the<br />

basic setting menu, but only if there is a circulation<br />

pipe available. The circulation return temperature is<br />

controlled, which is measured at the cold water<br />

sensor. This temperature must be attained for the<br />

preset disinfection time period. Short-term lower<br />

temperature deviations are corrected. In total, the<br />

actual time that the set temperature was attained,<br />

is counted. Should the flow temperature for the<br />

control <strong>system</strong> not be achieved, a corresponding<br />

error message is sent to the information menu after<br />

30 minutes. During the disinfection of the hot water<br />

and circulation pipes, very high temperatures are<br />

achieved. There is therefore a danger of scalding!<br />

Qualified personnel should take the necessary<br />

precautions for the protection of persons and<br />

property!<br />

■ Factory setting ON/OFF<br />

Should the controller be set back to the original<br />

factory positions as on delivery, this menu item is to<br />

be activated.<br />

■ Release<br />

In order to „unlock“ the controller for different<br />

settings, the following should be done:<br />

Release by pressing the right key twice and<br />

“OFF” will flash. Press UP and DOWN and right<br />

key simultaneously for approx. 2s and release<br />

changes to „ON“. To subsequently leave the setting,<br />

press the left key.<br />

The same operating sequence is used to block<br />

access to the controller. Alternatively, this takes<br />

place automatically after 60 minutes.<br />

2) This is executable within one minute after mains<br />

connection or by using the key combination. Access<br />

is automatically blocked after 60 minutes.<br />

3) Only possible to activate „release” by using the<br />

key combination in the menu. Access is automatically<br />

blocked after 60 minutes.