5. Control <strong>system</strong><br />
If a buffer sensor T5 is available as an option for the<br />
activation of the reheating function and its temperature<br />
is less than the circulation temperature + 2K, the<br />
circulation is then discontinued.<br />
As a result of the reheating function it is to be assumed<br />
that after reheating and for a conceivable period of<br />
time thereafter sufficient temperature is available in the<br />
buffer.<br />
Outside the active time slot, the circulation is always<br />
in the “pulse generated” mode, i.e. always when a<br />
drawing off of approx. 1 s has been carried out, the<br />
circulation pump is switched on for the programmed<br />
time in “circulation-running time” and the circulation is<br />
then also blocked from being reactivated for the preset<br />
“circulation-rest time” period.<br />
Circulation running time = 300 s<br />
From 0 – 600 s adjustable running time of the circulation<br />
pump.<br />
Circulation rest time = 5 min<br />
From 0 – 120 min adjustable blocking time for<br />
reactivating the circulation.<br />
Circulation hot water set value = 40°C<br />
From 10°C to 50°C adjustable temperature for circulation<br />
in the time slot.<br />
Sensor TF3 = select sensor T3 or T6 (optional)<br />
In the factory setting T3 is used for measuring the<br />
circulation temperature. However, an independent<br />
sensor T6 (optional) can also be used directly in the<br />
circulation pipes for this purpose.<br />
Option T5: With an additional sensor T5 (optional),<br />
which is installed in the buffer, two further functions<br />
can be activated.<br />
■ Activation T5<br />
If the activation T5 = on is selected, it is possible to<br />
only put the control <strong>system</strong> into operation after a<br />
specified buffer temperature has been attained.<br />
Factory setting = off<br />
Switch-on temperature = 35°C temperature<br />
(adjustment range 35°C to 55°C)<br />
Hysteresis = 3 K<br />
(adjustment range 3 K to 10 K)<br />
■ Reheating ON/OFF<br />
Optionally the additional „reheating” function can be<br />
activated. When there is a deviation lower than an<br />
adjustable set value for the buffer, this function is an<br />
external heat source which is activated to reheat<br />
the buffer until it reaches the set level.<br />
The requirement for this is that the heat source is<br />
actually able to supply the desired temperature level.<br />
For this purpose the contact S1 on the controller<br />
circuit board is used. This contact can be charged<br />
with 4 A 230 V AC. The set value for the storage<br />
temperature can be defined as an absolute value<br />
(fixed value e.g.: 65°C) or as a relative value.<br />
10<br />
Should the relative value be used, the set value for<br />
the buffer temperature is calculated from the<br />
programmed hot water – set temperature + the<br />
entered value for the „splay”. e.g.: hot water set<br />
temperature 50°C + splay 20 K = 70°C buffer<br />
temperature. Should the programmed or calculated<br />
set value deviate lower by 3 K, the external heat<br />
source is kept activated until the set value is reached<br />
again. The temperature values needed for this can be<br />
set in the programming menu, under the submenu<br />
“reheating”. (See 5.3.3)<br />
■ Pre-mixer ON/OFF<br />
As a rule, this selection is not active in this control<br />
<strong>system</strong>!<br />
■ Disinfection<br />
The “disinfection” function can be activated in the<br />
basic setting menu, but only if there is a circulation<br />
pipe available. The circulation return temperature is<br />
controlled, which is measured at the cold water<br />
sensor. This temperature must be attained for the<br />
preset disinfection time period. Short-term lower<br />
temperature deviations are corrected. In total, the<br />
actual time that the set temperature was attained,<br />
is counted. Should the flow temperature for the<br />
control <strong>system</strong> not be achieved, a corresponding<br />
error message is sent to the information menu after<br />
30 minutes. During the disinfection of the hot water<br />
and circulation pipes, very high temperatures are<br />
achieved. There is therefore a danger of scalding!<br />
Qualified personnel should take the necessary<br />
precautions for the protection of persons and<br />
property!<br />
■ Factory setting ON/OFF<br />
Should the controller be set back to the original<br />
factory positions as on delivery, this menu item is to<br />
be activated.<br />
■ Release<br />
In order to „unlock“ the controller for different<br />
settings, the following should be done:<br />
Release by pressing the right key twice and<br />
“OFF” will flash. Press UP and DOWN and right<br />
key simultaneously for approx. 2s and release<br />
changes to „ON“. To subsequently leave the setting,<br />
press the left key.<br />
The same operating sequence is used to block<br />
access to the controller. Alternatively, this takes<br />
place automatically after 60 minutes.<br />
2) This is executable within one minute after mains<br />
connection or by using the key combination. Access<br />
is automatically blocked after 60 minutes.<br />
3) Only possible to activate „release” by using the<br />
key combination in the menu. Access is automatically<br />
blocked after 60 minutes.