7. System examples<br />
7.7 Disinfecting the hot water<br />
and circulation pipes<br />
During the disinfection of the hot water and circulation<br />
pipes, very high temperatures are generated.<br />
There is a danger of scalding!<br />
Qualified personnel should take the necessary<br />
precautions for the protection of persons and property!<br />
8. Releasing operating level for specialist<br />
tradesmen!<br />
■ In the basic setting menu press the „down“ key<br />
downwards nine times until submenu release is<br />
attained [values].<br />
■ Now press „right” key twice, this causes “off” to<br />
flash.<br />
■ Press the „up“ and „down“ and „right“ keys<br />
simultaneously for approx. 2 s, release switches<br />
to “on”.<br />
■ Thereafter leave the menu by using the “left” key.<br />
The releasing of the operating level can be reset again in the same way.<br />
Access to the adjustable values is blocked automatically after 60 minutes!<br />
Example for setting the control <strong>system</strong>:<br />
1. Release the operating level for the specialist<br />
tradesmen in the basic setting menu.<br />
2. In the basic setting menu, submenu<br />
disinfection, select “in”.<br />
3. Set the hot water set value.<br />
Adjustment range 65 - 75°C<br />
4. Select disinfection time (duration of<br />
disinfection) Adjustment range 0 - 60 minutes<br />
5. Select the day, week day or daily.<br />
6. Start time (0 - 24 hours)<br />
This function should be deactivated after<br />
disinfection! The function is described in<br />
5.3.5!<br />
17