7. System examples<br />

7.7 Disinfecting the hot water<br />

and circulation pipes<br />

During the disinfection of the hot water and circulation<br />

pipes, very high temperatures are generated.<br />

There is a danger of scalding!<br />

Qualified personnel should take the necessary<br />

precautions for the protection of persons and property!<br />

8. Releasing operating level for specialist<br />

tradesmen!<br />

■ In the basic setting menu press the „down“ key<br />

downwards nine times until submenu release is<br />

attained [values].<br />

■ Now press „right” key twice, this causes “off” to<br />

flash.<br />

■ Press the „up“ and „down“ and „right“ keys<br />

simultaneously for approx. 2 s, release switches<br />

to “on”.<br />

■ Thereafter leave the menu by using the “left” key.<br />

The releasing of the operating level can be reset again in the same way.<br />

Access to the adjustable values is blocked automatically after 60 minutes!<br />

Example for setting the control <strong>system</strong>:<br />

1. Release the operating level for the specialist<br />

tradesmen in the basic setting menu.<br />

2. In the basic setting menu, submenu<br />

disinfection, select “in”.<br />

3. Set the hot water set value.<br />

Adjustment range 65 - 75°C<br />

4. Select disinfection time (duration of<br />

disinfection) Adjustment range 0 - 60 minutes<br />

5. Select the day, week day or daily.<br />

6. Start time (0 - 24 hours)<br />

This function should be deactivated after<br />

disinfection! The function is described in<br />

5.3.5!<br />

17