7. System examples<br />

7.1 Freshwater station with<br />

circulation in a time-slot<br />

and with tapping detection<br />

outside the time slot<br />

■ Initial operation and <strong>system</strong> calibration from point 6<br />

■ Setting the time and date, point 5.3.3<br />

■ Domestic hot ■ set value e.g.: 50°C, point<br />

water 5.3.3 and 5.3.5<br />

■ Circulation ■ Basic setting menu,<br />

Circulation submenu = select<br />

“on”, point 5.3.5<br />

■ In programming menu,<br />

circulation submenu up<br />

to 3 select time slot,<br />

point 5.3.3<br />

■ Circulation temperature 40°C,<br />

for control in time slot,<br />

point 5.3.5<br />

■ Circulation time e.g.: 60 s,<br />

Circulation rest time.: e.g.<br />

10 min, for controlling the<br />

circulation through tapping<br />

detection outside the<br />

time slot, point 5.3.5<br />

■ Heat transfer unit ■ WT = cold, point 5.3.3<br />

■ Time lag ■ e.g.: 20 s, point 5.3.5<br />

7.2 Freshwater station with<br />

circulation only via tapping<br />

detection<br />

■ Initial operation and <strong>system</strong> calibration from point 6<br />

■ Setting the time and date, point 5.3.3<br />

■ Domestic hot ■ set value e.g.: 50°C,<br />

water point 5.3.3 and 5.3.5<br />

■ Circulation ■ Basic setting menu,<br />

Circulation submenu = select<br />

“on”, point 5.3.5<br />

■ In programming menu,<br />

Circulation submenu is the<br />

start and stop times within<br />

each 3 time slots which are<br />

to be set at the same time<br />

e.g.: start 6h00 - stop 6h00<br />

point 5.3.3<br />

■ Circulation time e.g.: 60 s,<br />

Circulation rest time e.g.:<br />

10 min, point 5.3.5<br />

■ Heat transfer unit ■ WT = cold, point 5.3.3<br />

■ Time lag ■ e.g.: 20 s, point 5.3.5<br />

14<br />

7.3 Freshwater station without<br />

circulation<br />

■ Initial operation and <strong>system</strong> calibration from point 6<br />

■ Setting the time and date, point 5.3.3<br />

■ Domestic hot ■ set value e.g.: 50°C, point<br />

water 5.3.3 and 5.3.5<br />

■ Circulation ■ Basic setting menu,<br />

Circulation submenu = select<br />

“off”, point 5.3.5<br />

■ Heat transfer unit ■ WT = cold can be selected,<br />

if the distance between<br />

the buffer and the freshwater<br />

station is not too great.<br />

After-run e.g.: 20 s,<br />

point 5.3.5<br />

■ WT = hot can be selected,<br />

if there is a great distance<br />

between the buffer and the<br />

freshwater station, and the<br />

comfort of the “rapid” hot<br />

water drawing has been<br />

attained. Set the after-run<br />

point 5.3.5 on nought, as no<br />

circulation pipe is available.