9. Trouble-shooting<br />

The following is to be checked if the domestic hot water<br />

temperature is not reached:<br />

■ System voltage (fuses)<br />

■ Buffer temperature<br />

■ Vent the freshwater station<br />

■ A temperature sensor interruption or a short circuit<br />

is displayed in the information menu by a flashing<br />

general error message and is shown individually<br />

when requesting each sensor.<br />

■ Carry out characteristic curve calibration, from<br />

point 6.3.2.<br />

■ Carry out a circulation adjustment, point 6.3.3.<br />

■ During a hot water withdrawal, the circulation pipe<br />

becomes cold.<br />

Cause: The return flow preventer in the connecting<br />

nipple above the circulation pump can start leaking<br />

due to soiling in the cold water network.<br />

■ Flow rate metre: To check this, a hot water tapping<br />

is required and the flow in litres per minute read in<br />

the information menu. An intact flow rate metre<br />

should show a relatively constant value. Should<br />

fluctuations occur, check whether this comes from<br />

the domestic water network, for example in pressure<br />

increase <strong>system</strong>s<br />

■ Set the freshwater station according to the <strong>system</strong><br />

examples.<br />

■ The pumps P1 and P2 run alternatively and the status<br />

display in the information menu switches between<br />

active 50, after-run and off.<br />

■ Carry out a circulation adjustment, point 6.3.3.<br />

■ After several months of smooth running operation<br />

the hot water capacity is no longer reached.<br />

■ If a dirt filter has been installed in front of the<br />

station, this should be cleaned.<br />

■ Check return flow preventer.<br />

■ Vent the buffer and the freshwater station<br />

18<br />

■ A short time after drawing off hot water at the tap<br />

(e.g.: washbasin) the hot water temperature drops<br />

sharply even though the control <strong>system</strong> displays<br />

e.g.: 50°C hot water temperature.<br />

■ The return flow preventer should be checked in<br />

the connecting nipple above the circulation pump<br />

to see if it leaks as a result of soiling in the cold<br />

water <strong>system</strong> and if cold water has been<br />

pressed into the circulation piping.<br />

■ The circulation does not work:<br />

■ Carry out circulation adjustment!<br />

■ Check time slot!<br />

■ The temperature of the heat transfer media<br />

in the buffer is too low.<br />

The circulation set temperature + 2 K is not<br />

being reached at T2 or at T5, if present.<br />

(see point 5.3.5 Circulation)<br />

Please ensure that there is a sufficient quantity<br />

of heat in the buffer!<br />

With option T5 „reheat buffer“, a type of boiler<br />

can be activated.