9. Trouble-shooting<br />
The following is to be checked if the domestic hot water<br />
temperature is not reached:<br />
■ System voltage (fuses)<br />
■ Buffer temperature<br />
■ Vent the freshwater station<br />
■ A temperature sensor interruption or a short circuit<br />
is displayed in the information menu by a flashing<br />
general error message and is shown individually<br />
when requesting each sensor.<br />
■ Carry out characteristic curve calibration, from<br />
point 6.3.2.<br />
■ Carry out a circulation adjustment, point 6.3.3.<br />
■ During a hot water withdrawal, the circulation pipe<br />
becomes cold.<br />
Cause: The return flow preventer in the connecting<br />
nipple above the circulation pump can start leaking<br />
due to soiling in the cold water network.<br />
■ Flow rate metre: To check this, a hot water tapping<br />
is required and the flow in litres per minute read in<br />
the information menu. An intact flow rate metre<br />
should show a relatively constant value. Should<br />
fluctuations occur, check whether this comes from<br />
the domestic water network, for example in pressure<br />
increase <strong>system</strong>s<br />
■ Set the freshwater station according to the <strong>system</strong><br />
examples.<br />
■ The pumps P1 and P2 run alternatively and the status<br />
display in the information menu switches between<br />
active 50, after-run and off.<br />
■ Carry out a circulation adjustment, point 6.3.3.<br />
■ After several months of smooth running operation<br />
the hot water capacity is no longer reached.<br />
■ If a dirt filter has been installed in front of the<br />
station, this should be cleaned.<br />
■ Check return flow preventer.<br />
■ Vent the buffer and the freshwater station<br />
18<br />
■ A short time after drawing off hot water at the tap<br />
(e.g.: washbasin) the hot water temperature drops<br />
sharply even though the control <strong>system</strong> displays<br />
e.g.: 50°C hot water temperature.<br />
■ The return flow preventer should be checked in<br />
the connecting nipple above the circulation pump<br />
to see if it leaks as a result of soiling in the cold<br />
water <strong>system</strong> and if cold water has been<br />
pressed into the circulation piping.<br />
■ The circulation does not work:<br />
■ Carry out circulation adjustment!<br />
■ Check time slot!<br />
■ The temperature of the heat transfer media<br />
in the buffer is too low.<br />
The circulation set temperature + 2 K is not<br />
being reached at T2 or at T5, if present.<br />
(see point 5.3.5 Circulation)<br />
Please ensure that there is a sufficient quantity<br />
of heat in the buffer!<br />
With option T5 „reheat buffer“, a type of boiler<br />
can be activated.