6. Initial operation and <strong>system</strong> calibration<br />
6.3.3 Circulation adjustment<br />
A circulation adjustment is to be undertaken if the<br />
freshwater station is fitted with a circulation pump and<br />
a circulation pipe is connected to it! For the controller to<br />
detect a withdrawal of water, the actual circulation cycle<br />
must be known as the flow rate is always measured by<br />
the sum of the hot water withdrawal and the overlaying<br />
circulation.<br />
Information for a software update:<br />
As of software version V 1.54 the 3 l/min flow rate<br />
restrictor can be left out.<br />
A prerequisite for the calibration is that all hot water<br />
tapping points are closed.<br />
Procedure to be followed:<br />
■ select: manual menu<br />
■ menu item „circulation adjustment“<br />
■ select by using the right key,<br />
„OFF“ flashes<br />
■ using the „UP“ key change to „ON“<br />
■ confirm twice using the right key<br />
■ the message “flowing” is displayed<br />
■ when the message „Circulation calibration<br />
complete“ is displayed, measuring has been<br />
finished. The measured value is displayed<br />
and independently logged into the control<br />
<strong>system</strong>.<br />
■ Leave the menu using the left key<br />
12