6. Initial operation and <strong>system</strong> calibration<br />

6.3.3 Circulation adjustment<br />

A circulation adjustment is to be undertaken if the<br />

freshwater station is fitted with a circulation pump and<br />

a circulation pipe is connected to it! For the controller to<br />

detect a withdrawal of water, the actual circulation cycle<br />

must be known as the flow rate is always measured by<br />

the sum of the hot water withdrawal and the overlaying<br />

circulation.<br />

Information for a software update:<br />

As of software version V 1.54 the 3 l/min flow rate<br />

restrictor can be left out.<br />

A prerequisite for the calibration is that all hot water<br />

tapping points are closed.<br />

Procedure to be followed:<br />

■ select: manual menu<br />

■ menu item „circulation adjustment“<br />

■ select by using the right key,<br />

„OFF“ flashes<br />

■ using the „UP“ key change to „ON“<br />

■ confirm twice using the right key<br />

■ the message “flowing” is displayed<br />

■ when the message „Circulation calibration<br />

complete“ is displayed, measuring has been<br />

finished. The measured value is displayed<br />

and independently logged into the control<br />

<strong>system</strong>.<br />

■ Leave the menu using the left key<br />

12