10. Factory setting and personal setting<br />

Menu Submenu<br />

Heat transfer unit<br />

Circulation<br />

Circulation<br />

adjustment<br />

Factor<br />

setting<br />

Hot water set value 50°C<br />

Water temperature (WT)<br />

operating mode hot / cold / timed<br />

heating<br />

cold<br />

Hot water set value 40°C<br />

Water temperature hysteresis 3 K<br />

Hot water max 5 K<br />

Hot water min -5 K<br />

Test time 5 min<br />

Time slot 1<br />

Time slot 2<br />

Time slot 3<br />

Volumetric flow rate<br />

Circulation<br />

6:00 - 9:00<br />

11:00 - 13:00<br />

16:00 - 20:00<br />

Pulse generator 72 lmp. / litre<br />

Characteristic curve<br />

Flow min 4 l/min<br />

Capacity min 8 %<br />

Flow middle 8 l/min<br />

Capacity middle 20 %<br />

Flow max 25 l/min<br />

Capacity max 76 %<br />

Correction 5 K 10 %<br />

Heat transfer media adjustment 75°C<br />

Temperature - cold water adjustment 15°C<br />

Se value adjustment 50°C<br />

Heat transfer unit After - run 20 s<br />

Circulation<br />

Activation T5<br />

3 l<br />

On/Off on<br />

Running time 90 s<br />

Rest time 0 min<br />

Set value 40°C<br />

Flow increase circulation 5 K<br />

Temperature sensor 3 or 6 TF3<br />

On or Off Off<br />

Temperature 35°C<br />

Hysteresis 3 K<br />

Reheating On/Off Off<br />

absolute or relative absolute<br />

Pre-mixer On/Off Off<br />

Disinfection On/Off Off<br />

Hot water set value Off<br />

Disinfection time 70°C<br />

Start Monday<br />

Start 1:00<br />

UPS 15-60 Pump stage 2<br />

Personal<br />

setting<br />

19