3. Equipment and functional description<br />
■ The freshwater station allows for a hygienic and<br />
energy-saving preparation of warm water via a<br />
stainless steel plate heat exchanger. It provides fresh<br />
hot water for one to two apartment units. The source<br />
of supply is a storage tank with a variable temperature<br />
of 60 to 95°C. At very high storage temperatures<br />
(up to 95°C) a temperature reduction of the<br />
heat transfer media is recommended by admixture.<br />
The primary pump P1 is controlled via block<br />
modulation in such a way that the desired hot water<br />
temperature is kept constant as much as possible.<br />
For the control <strong>system</strong> to calculate the necessary<br />
pump capacity, it uses the heat transfer media<br />
temperature on the primary side, the inlet temperature<br />
of the cold water and the circulation on the<br />
secondary side as well as the current flow.<br />
■ In addition to the preparation of freshwater, the<br />
circulation can also be activated. In the “basic<br />
setting” menu the circulation is switched ON or<br />
OFF.<br />
■ For circulation, up to 3 time slots can be specified in<br />
the “programming” menu.<br />
■ For the stainless steel plate heat exchanger there<br />
are three modes of operation besides the drawing of<br />
hot water:<br />
water temperature-cold, water temperature -hot<br />
and water temperature-timed heating<br />
(See 5.3.3).<br />
4<br />
■ After-run<br />
Should water temperature-cold be selected, it is<br />
possible to set the circulation pump at an after-run,<br />
to allow the stainless steel plate heat exchanger<br />
to cool down and to prevent calcification.<br />
The after-run function is however, only possible and<br />
meaningful outside the circulation time!<br />
■ Activating the hot water controller and reheating<br />
With the additional T5 sensor (not included in<br />
delivery), it is possible to put the control <strong>system</strong> in<br />
operation only after a specified buffer temperature<br />
has been attained. With the T5 sensor it is furthermore<br />
possible to activate a boiler for reheating via a<br />
potential-free contact. Both functions are deactivated<br />
in the factory setting.<br />
■ Disinfection<br />
With this function it is possible to disinfect the<br />
circulation pipes against the danger of legionella.<br />
This function is only activated when a circulation<br />
pipe is available and the circulation has been<br />
switched on.<br />
■ Data logging<br />
With a „data stick” all measured values and the<br />
status of pump outputs can be recorded for a<br />
specific time period. A special computer programme<br />
is used to analyse the measured values at the<br />
freshwater station manufacturer.<br />
T1 = Domestic hot water<br />
T2 = Heat transfer media flow<br />
T3 = Cold water and<br />
circulation temperature<br />
T4 = Heat transfer media return<br />
T5 = Storage tank sensor for<br />
„reheating“ and release of the<br />
hot water controller and<br />
circulation<br />
P1 = Primary heat transfer pump<br />
P2 = Circulation pump<br />
DFZ = Flow rate metre<br />
1 = Heat transfer unit<br />
2 = Return flow preventer<br />
3 = Control<br />
4 = Shut-off valve<br />
5 = Flow rate restrictor 3l<br />
6 = Filling and draining tap<br />
A = Flow heating<br />
B = Return heating<br />
C = Domestic hot water outlet<br />
D = Hot water circulation<br />
E = Cold water (domestic water)