7. System examples<br />

7.6 Freshwater station as<br />

cascade connection<br />

Should larger volumes of hot water be needed, overflow<br />

valves allow for the interconnection of two or more<br />

freshwater stations as a cascade. Here, the service<br />

water circulation module can be left out for the second<br />

and other freshwater stations.<br />

The circulation is controlled only by the first freshwater<br />

station.<br />

Basic circuit diagram:<br />

Second station First station<br />

Required accessories:<br />

Overflow valve DN 25 for<br />

Cascade connection<br />

Adjustment range:<br />

100 to 500 mbar<br />

Article no.: 69072.9<br />

16<br />

Domestic water<br />

hot<br />

Domestic water<br />

cold<br />

7.6.1 Initial operation and<br />

<strong>system</strong> calibration of the<br />

freshwater cascade<br />

First station<br />

■ Initial operation and <strong>system</strong> calibration from point 6<br />

■ Setting the time and date, point 5.3.3<br />

■ Domestic hot ■ set value e.g.: 50°C, point<br />

water 5.3.3 and 5.3.5<br />

■ Circulation ■ Basic setting menu,<br />

Circulation submenu = select<br />

“on”, point 5.3.5<br />

■ In programming menu,<br />

circulation submenu up to<br />

3 select time slot, point 5.3.3<br />

■ Circulation temperature<br />

40°C, for control in time slot,<br />

point 5.3.5<br />

■ Circulation time e.g.: 60 s,<br />

Circulation rest time.: e.g.<br />

10 min, for controlling the<br />

circulation through tapping<br />

detection outside the time<br />

slot, point 5.3.5<br />

■ Heat transfer unit ■ WT = cold, point 5.3.3<br />

■ Time lag ■ e.g.: 20 s, point 5.3.5<br />

Second station<br />

■ Initial operation and <strong>system</strong> calibration:<br />

The determined values of the characteristic curve<br />

calibration of the first station are taken over. These<br />

values are read in the first control <strong>system</strong> in the<br />

basic setting menu, characteristic curve submenu<br />

and in the same menu they are set in the second<br />

control <strong>system</strong>.<br />

■ Setting the time and date, point 5.3.3<br />

■ Domestic hot ■ Set value e.g.: 50°C,<br />

water point 5.3.3 and 5.3.5<br />

■ Circulation off<br />

■ Heat transfer unit ■ WT = cold, point 5.3.3<br />

■ After-run ■ e.g.: 20 s, point 5.3.5<br />

Differential pressure-overflow valve<br />

Hot water should be drawn off of e.g.: 35l/min.<br />

This domestic water volumetric flow can be read in<br />

the control <strong>system</strong> information menu of the first<br />

freshwater station. Set the differential pressureoverflow<br />

valve so that the second freshwater station<br />

starts operating (determination of opening pressure of<br />

the overflow valve). Loosen the locking screw at the<br />

differential pressure-overflow valve. Afterwards the<br />

opening pressure can be adjusted in stages by turning<br />

the hand wheel valve. The selected position should<br />

subsequently be checked at the locking screw to<br />

ensure it against accidental adjustment.