6. Initial operation and <strong>system</strong> calibration<br />

6.3.4 Detailed description of<br />

characteristic curve<br />

calibration<br />

Characteristic<br />

curve off<br />

calibrate<br />

Characteristic<br />

curve on<br />

calibrate<br />

Withdrawal<br />

starts<br />

Determining the operating points of the<br />

control <strong>system</strong><br />

■ Manual operation menu<br />

■ Characteristic curve calibration submenu<br />

1x Leave the info menu using the “escape” key<br />

2x<br />

flashes<br />

5x<br />

and then<br />

1x<br />

flashes<br />

1x<br />

2x<br />

1x<br />

Select the menu: manual operation<br />

Select the menu: manual operation<br />

■ select using right key, OFF flashes.<br />

■ Using the upper key, switch to On and<br />

■ confirm twice with the right key.<br />

Calibration procedure starts.<br />

Kindly follow the menu guidance on the<br />

display.<br />

Consecutive drawn amounts of 25 litres,<br />

8 litres and 4 litres are required. After the<br />

relevant operating points of the pump have<br />

been determined and independently logged<br />

into the control <strong>system</strong>, characteristic curve<br />

calibration “on” again appears on the display.<br />

Leave this submenu using the left key.<br />

The characteristic curve calibration is now<br />

complete.<br />