YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
5. Control <strong>system</strong><br />
5.3.1 Explanation of menu items<br />
5.3.2 Information menu<br />
In this menu all the measured values of the temperature<br />
sensor, volumetric flow metre as well as the control<br />
<strong>system</strong> (<strong>system</strong> conditions) are displayed.<br />
Status display:<br />
Active 50 = Control <strong>system</strong> on domestic hot water<br />
set temperature value of 50°C<br />
Z - active 4 = Control <strong>system</strong> on circulation set<br />
temperature value of 40°C<br />
After-run = After-run of the circulation pump for<br />
cooling down the stainless steel plate<br />
heat exchanger (See 5.3.5)<br />
Disinfection = Control <strong>system</strong> on disinfection<br />
temperature<br />
Off = No control <strong>system</strong> function active<br />
5.3.3 Programming menu<br />
The programming menu contains values which are to be<br />
set by the end customer.<br />
■ Heat transfer unit<br />
Hot water – set value 50°C, adjustment range<br />
45°C to 60°C for domestic hot water. Should this<br />
value be increased, the 60°C temperature value of<br />
the safety shutdown should also be increased, by<br />
going in the basic setting menu, submenu<br />
„Controller“. A blending valve should in any event be<br />
installed on the freshwater station outlet!<br />
Water temperature – operating mode:<br />
cold, hot or timed heating.<br />
Water temperature – cold 1) No heat exchange<br />
media is added to the stainless steel plate heat<br />
exchanger after hot water has been drawn off. It<br />
remains at the lowest temperature level after<br />
drawing off. This results in a favourable control<br />
behaviour arising for the drawing off of hot water.<br />
Water temperature – hot 1) 2) The stainless steel<br />
plate heat exchanger is continuously kept at a<br />
constant operating temperature. When there is a<br />
deviation lower than the water temperature set value<br />
minus hysteresis, the P1 is activated with a capacity<br />
of 25 % until the water temperature set value has<br />
been achieved. This happens provided that a temperature<br />
is measured at T2 or at the “reheating” option<br />
at T5 which is greater than that of the hold-warm<br />
temperature. Should this condition not be fulfilled at<br />
T2, the temperature is again requested after a resting<br />
period of one hour.<br />
Water temperature – timed heating 1) 2) For the<br />
duration of the time slot the stainless steel plate<br />
heat exchanger is kept warm.<br />
8<br />
Water temperature – set value 2) 40°C, adjustment<br />
range 20°C to 50°C for the hold-warm temperature<br />
of the stainless steel plate heat exchanger for water<br />
temperature – hot and water temperature – timed<br />
heating.<br />
Water temperature – Hysteresis 3 K, adjustment<br />
range 1 K to 20 K for the water temperature set<br />
value. Only visible if water temperature = hot or<br />
water temperature = timed heating has been<br />
selected!<br />
Note: The water temperature – hot function should<br />
be used if the buffer storage is located far from<br />
the freshwater station and the <strong>system</strong> is<br />
operated without circulation.<br />
Hot water max. 5K (2 K – 10 K)<br />
Hot water min. 5K (2 K – 10 K)<br />
Testing period 5 min (1 min – 30 min)<br />
An error message is displayed when the temperature<br />
exceeds or is lower than the hot water set<br />
value. When the threshold values are exceeded or<br />
the temperature drops below these values, a fault is<br />
generated after the preset monitoring period, and<br />
output S2 is switched as a potential-free contact.<br />
The output is reset once the temperature is again<br />
within the temperature range or it can be reset in<br />
the information menu/error message upon actuation<br />
of the right key. This monitoring is only valid when<br />
drawing off takes place – not during circulation!<br />
■ Time slot<br />
There are tree time slots available to set the<br />
circulation. Should the switch-on and the switch-off<br />
time be set the same, this time slot is no longer<br />
active. For further circulation functions, see 5.3.3.<br />
The time slots are also used for the water tempera-<br />
ture - timed heating. (See 5.3.3)<br />
■ Reheating<br />
This menu item is only visible once the reheating<br />
function has been activated in the basic setting<br />
menu. If „absolute value” has been selected, „65°C<br />
storage tank set value” will be displayed. This value<br />
is adjustable between 20°C and 90°C. If „relative<br />
value” is selected „15 K splay” is displayed here.<br />
This value is adjustable between 2 K and 50 K.<br />
For further information regarding functions, see<br />
points 5.3.5 and 7.4. Storage tank set value = buffer<br />
set value<br />
■ Data logging<br />
This menu is only visible if a data stick has been<br />
connected to the front side of the control <strong>system</strong>.<br />
Measured values can be recorded on this data stick.<br />
In a measurement interval of 1 second (factory<br />
setting) measured values for approx. 4.5 hours can<br />
be logged. The data can be analysed at the plant<br />
with special software.<br />
■ Clock time<br />
Submenu for setting the clock time, date and the day<br />
of the week.