5. Control <strong>system</strong><br />

5.3.1 Explanation of menu items<br />

5.3.2 Information menu<br />

In this menu all the measured values of the temperature<br />

sensor, volumetric flow metre as well as the control<br />

<strong>system</strong> (<strong>system</strong> conditions) are displayed.<br />

Status display:<br />

Active 50 = Control <strong>system</strong> on domestic hot water<br />

set temperature value of 50°C<br />

Z - active 4 = Control <strong>system</strong> on circulation set<br />

temperature value of 40°C<br />

After-run = After-run of the circulation pump for<br />

cooling down the stainless steel plate<br />

heat exchanger (See 5.3.5)<br />

Disinfection = Control <strong>system</strong> on disinfection<br />

temperature<br />

Off = No control <strong>system</strong> function active<br />

5.3.3 Programming menu<br />

The programming menu contains values which are to be<br />

set by the end customer.<br />

■ Heat transfer unit<br />

Hot water – set value 50°C, adjustment range<br />

45°C to 60°C for domestic hot water. Should this<br />

value be increased, the 60°C temperature value of<br />

the safety shutdown should also be increased, by<br />

going in the basic setting menu, submenu<br />

„Controller“. A blending valve should in any event be<br />

installed on the freshwater station outlet!<br />

Water temperature – operating mode:<br />

cold, hot or timed heating.<br />

Water temperature – cold 1) No heat exchange<br />

media is added to the stainless steel plate heat<br />

exchanger after hot water has been drawn off. It<br />

remains at the lowest temperature level after<br />

drawing off. This results in a favourable control<br />

behaviour arising for the drawing off of hot water.<br />

Water temperature – hot 1) 2) The stainless steel<br />

plate heat exchanger is continuously kept at a<br />

constant operating temperature. When there is a<br />

deviation lower than the water temperature set value<br />

minus hysteresis, the P1 is activated with a capacity<br />

of 25 % until the water temperature set value has<br />

been achieved. This happens provided that a temperature<br />

is measured at T2 or at the “reheating” option<br />

at T5 which is greater than that of the hold-warm<br />

temperature. Should this condition not be fulfilled at<br />

T2, the temperature is again requested after a resting<br />

period of one hour.<br />

Water temperature – timed heating 1) 2) For the<br />

duration of the time slot the stainless steel plate<br />

heat exchanger is kept warm.<br />

8<br />

Water temperature – set value 2) 40°C, adjustment<br />

range 20°C to 50°C for the hold-warm temperature<br />

of the stainless steel plate heat exchanger for water<br />

temperature – hot and water temperature – timed<br />

heating.<br />

Water temperature – Hysteresis 3 K, adjustment<br />

range 1 K to 20 K for the water temperature set<br />

value. Only visible if water temperature = hot or<br />

water temperature = timed heating has been<br />

selected!<br />

Note: The water temperature – hot function should<br />

be used if the buffer storage is located far from<br />

the freshwater station and the <strong>system</strong> is<br />

operated without circulation.<br />

Hot water max. 5K (2 K – 10 K)<br />

Hot water min. 5K (2 K – 10 K)<br />

Testing period 5 min (1 min – 30 min)<br />

An error message is displayed when the temperature<br />

exceeds or is lower than the hot water set<br />

value. When the threshold values are exceeded or<br />

the temperature drops below these values, a fault is<br />

generated after the preset monitoring period, and<br />

output S2 is switched as a potential-free contact.<br />

The output is reset once the temperature is again<br />

within the temperature range or it can be reset in<br />

the information menu/error message upon actuation<br />

of the right key. This monitoring is only valid when<br />

drawing off takes place – not during circulation!<br />

■ Time slot<br />

There are tree time slots available to set the<br />

circulation. Should the switch-on and the switch-off<br />

time be set the same, this time slot is no longer<br />

active. For further circulation functions, see 5.3.3.<br />

The time slots are also used for the water tempera-<br />

ture - timed heating. (See 5.3.3)<br />

■ Reheating<br />

This menu item is only visible once the reheating<br />

function has been activated in the basic setting<br />

menu. If „absolute value” has been selected, „65°C<br />

storage tank set value” will be displayed. This value<br />

is adjustable between 20°C and 90°C. If „relative<br />

value” is selected „15 K splay” is displayed here.<br />

This value is adjustable between 2 K and 50 K.<br />

For further information regarding functions, see<br />

points 5.3.5 and 7.4. Storage tank set value = buffer<br />

set value<br />

■ Data logging<br />

This menu is only visible if a data stick has been<br />

connected to the front side of the control <strong>system</strong>.<br />

Measured values can be recorded on this data stick.<br />

In a measurement interval of 1 second (factory<br />

setting) measured values for approx. 4.5 hours can<br />

be logged. The data can be analysed at the plant<br />

with special software.<br />