Heater Option Operation:<br />
The Heater option contains all the required components to maintain the batteries at a constant<br />
temperature of 25 deg. C or 77 deg. F. It comes pre-wired and programmed and should require no<br />
operator interface.<br />
To turn the heater option on, simply turn on it’s dedicated circuit breaker located on the lower shelf<br />
containing all the AC circuit distribution.<br />
The Heater Option consists of a Temperature Controller, Solid State Switch, Temperature Sensor,<br />
and Heating Elements.<br />
The Temperature Controller is located in the upper left corner of the electronic shelf and its default<br />
display is the current temperature and programmed temperature. The programmed temperature is<br />
factory set to 25 deg. C or 77 deg. F.<br />
The Solid State Switch is located directly below the Controller and its function is to connect and<br />
disconnect power to the heating elements. The Solid State Switch is fed from a 120 VAC source. If<br />
your input power is not 120 VAC, there is a factory provided Isolation Transformer to provide the 120<br />
VAC to the Solid State Switch.<br />
The Temperature Sensor is an RTD type and is located in the cable bundle on the left side of the<br />
middle battery shelf.<br />
There are 48 heating elements divided equally through three battery shelves. Each battery shelf has<br />
16 heating elements producing 460 Watts. This 460 Watts is divided equally between 16 elements<br />
and provides an even distribution of heat over the entire surface of the shelf. This even distribution<br />
eliminates hot spots and uneven heat distribution between the batteries.<br />
The Temperature Controller is factory programmed and should only be changed by authorized<br />
factory personnel.<br />
62<br />