4.4 Installing the Auxiliary Thermocouple<br />

Weld a 1/2 inch BSP mounting socket to the flue within about 300 mm (12”), and upstream of the oxygen<br />

probe. The thermocouple should be of similar length to the oxygen probe to prevent flue temperature<br />

distribution errors.<br />

The thermocouple should be connected to terminals 7 & 8. These terminals will not be available for an<br />

auxiliary thermocouple if a second probe has been installed.<br />

4.5 Shield Connections<br />

All external wiring to the <strong>1735</strong> transmitter should be shielded. Do not connect shields at the field end.<br />

Simply clip off and insulate. There are two M4 earth screw terminals available in the <strong>1735</strong> transmitter. An<br />

extra terminal strip may be required to connect all shields together. This should be supplied by the installer.<br />

4.6 Earth Connection (PE)<br />

The PE (protective earth) input connection must be made to the earth stud on the right hand side of cabinet.<br />

The PE input connection must be the first connection onto the earth stud and it must be secured by a<br />

separate nut and spring washer. All other earth connections (bonding connections) can be made on either of<br />

the two earth studs in the base of the cabinet.<br />

The controller MUST be securely earthed.<br />

Right hand<br />

earth stud<br />

Incoming<br />

PE wire<br />

Other bonding<br />

earth wires<br />

Assembly of the PE and bonding connections on the earth stud<br />

April 2012<br />

22 <strong>1735</strong> Water Vapour Transmitter