NOTE: Hardware Protocol Selection<br />
The communications port of the <strong>1735</strong> can be configured to communicate on either RS232 or RS485. If the<br />
transmitter is to be used on a MODBUS network, the <strong>1735</strong> transmitter must be set to RS485. For further<br />
details see chapter 7.2.26, Communication Port Options.<br />
NOTE: Terminating Resistor<br />
There is a terminating 100 ohm resistor fitted to the 1730-1 PCB. Link LK3 (TERM), in the bottom left-hand<br />
corner of the PCB, is used to connect the terminating resistor. Link LK3 must be removed on all transmitters<br />
except the transmitter on the end of the network line. If the network line from the transmitters is taken from<br />
the middle of the transmitter network string, a terminating resistor should be enabled with LK3 at each end of<br />
the network line.<br />
The MODBUS protocol of the network is –<br />
Baud Rate 19,200<br />
Parity<br />
None<br />
Stop Bits 1<br />
RS485 Half Duplex<br />
Mode<br />
RTU (binary mode)<br />
For more details see Appendix 3.<br />
Oxygen Transmitter #1<br />
Network Master<br />
Network -<br />
Network +<br />
Network Com.<br />
20 Network -<br />
21 Network +<br />
22 Network Com<br />
Oxygen Transmitter #2<br />
20 Network -<br />
21 Network +<br />
22 Network Com<br />
Oxygen Transmitter #xx<br />
20 Network -<br />
21 Network +<br />
22 Network Com<br />
Network Connections<br />
April 2012<br />
30 <strong>1735</strong> Water Vapour Transmitter