LEGENDLRA - Locked Rotor AmpsMCC - Maxmium Continuous CurrentRLA - Rated Load AmpsNOTES:1. RLA (rated load amps) value shown for new high efficiency models is MCC ÷ 1.56 = RLA. Use thisrecommended (and minimum) RLA value to determine nameplate stamping. Minimum contactor sizing and wire sizing.2. Compressor operating amps at any specific conditions can only be determined from a performance curve.3. RLA values for 06D compressor protected by a calibrated circuit breaker will depend on must-trip value of circuit breaker.4. Ohm values shown for resistance are approximate and shown for reference only. Motors from different vendors and motors of different efficienciescan differ up to 15% from data shown.105OPERATING RANGESALLOWABLENOMINALVOLTAGE MAXIMUM MINIMU M187414518342180254529661460230208/230460575400 (50 Hz)200 (50 Hz)