COMPRESSOR ISOLATIONIf you have determined there is no refrigerant leakaround the terminals and the compressor must be replaced,proceed beginning with Step 1:1. Shut off suction and discharge service valves to isolatecompressor and slowly remove all refrigerant in compressor.Appropriate service practices should be followedto properly reclaim refrigerant removed from thecompressor.2. Disconnect all electrical wiring to compressor.3. Unbolt suction and discharge service valves fromcompressor.REMINDER: These valves may be sealing off refrigerantfrom the rest of the system. Do not open these valveswithout first determining whether there is refrigerant inthe system.21