Appendix No. 6<br />

to Certificate of <strong>Co</strong>nformity:<br />

Terminal coolent of enclosure type:<br />

Enclosure dimension in mrn:<br />

<strong>KEMA</strong> 99ATEX7540 X<br />

<strong>KEMA</strong>~<br />

~310.ll8I2AR Am"""<br />

PostbUs 9035. NL -6800 Ef Amhem<br />

NexT 503520<br />

H= 500 W= 350 D= 205<br />

The table shows the maximum number of conductors depending on the cable size and permitted<br />

current for the above mentioned enclosure.<br />

"<strong>Co</strong>nductor" means every conductor entering the enc10sure and every internal connecting<br />

conductor. Any cross connections or earth terminals are not counted.<br />

Current 1.5 2.5 10 16<br />

(Amps)<br />

8 237<br />

1 115<br />

1 39 76 298<br />

2 16 45 86<br />

25 21 49 94<br />

35 14 37 91<br />

5 5 30 76<br />

63 10 35<br />

8 13<br />

1<br />

125<br />

1<br />

2<br />

225 The terminal conten! in this<br />

25 area requires apower<br />

315 dissipation test reporl from<br />

40 the manufacturer<br />

50<br />

70 95 120 150 185 240<br />

In /his area yau can add as many<br />

terminals as physically possible.<br />

125<br />

39 140<br />

16 37<br />

15 37<br />

13 33<br />

12 28<br />

4 16<br />

8<br />

Maximum physical terminal coolent depends on the terminal dimension and<br />

the maximum permissibte cable size used.<br />

88<br />

34<br />

21 44<br />

4 12 26<br />

5 18<br />

2<br />

Note:<br />

Maximum permissible rated current of the applied terminals and cables must be taken<br />

into account. Cables used intemally must be suitable for a temperature between 70° and 80°C.<br />

For 1arger cables, the number of conductors must be advised by the manufacturer ( with Power<br />

Dissipation Test Report ).<br />

When using the table above, de-rating factors or nominal rated currents in accordance with<br />

IEC 439 shou1d be used.<br />

Different types of terminals can be used together by utilising the tabular values proportionally.<br />

Example: <strong>Co</strong>nductor Size Current Number Load